Plan Review Notes
Plan Review Notes For Permit 16041147
Permit Number 16041147
Review Stop B
Sequence Number 3
Notes
Date Text
2016-10-24 17:16:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16041147
 ADD: 914 3RD ST.
 CONT: TREND WEST INC.
 TEL: 561-358-8817
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. OCT. 24 /2016
 ACTION: DENIED
  
 1) SHEET S1:
  
 1A)3RD REQUEST. THIS SHEET AND THE ELECTRICAL SHEETS
 SHOW 5 DWELLING UNITS, BUT THE DESIGNER OF RECORD MAKE
 NUMEROUS MENTION TO THE2014 RESIDENTIAL CODE. PLEASE
 NOTE THE FBC- RESIDENTIAL CODE IS FOR 1 & 2 FAMILY
 ONLY!!!!! PLEASE NOTE THIS 5 UNIT RESIDENTIAL STRUCTURE
 IS COVERED AND TO BE REVIEWED UNDER THE 2014
 FBC-BUILDING CODE- BUILDING CODE. PLEASE CORRECT THE
 CODE REFERENCES TO THE RESIDENTIAL CODE AND TABLES IN
 THE RESIDENTIAL CODE.
  
 2) 2014 FLORIDA BUILDING CODE- BUILDING, PLEASE PROVIDE
 THE WIND DESIGN CRITERIA UNDER 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 3) THE SUBMITTED PRODUCT APPROVAL (FL 12769 JELD WEN)
 WITHOUT SURFACE BOLTS IS GOOD FOR -50 PSF, THE DESIGNER
 OF RECORD INDICATES THE NEGATIVE PRESSURES FOR THIS
 OPENING ARE -52.7 FOR DOORS LOCATED IN A INTERIOR ZONE
 # 4. THE DESIGNER OF RECORD CAN BE MORE RESTRICTIVE
 THAN THE MINIMUM CODE. PRESSURES GIVEN ARE AT 132 VASD.
  
 4) THE DESIGNER OF RECORD HAS NOT APPLIED THEIR SHOP
 DRAWING STAMP OF APPROVAL ON THE PRODUCT APPROVAL
 SUBMITTED. FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  