2016-07-21 13:50:38 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16041147 |
| ADD: 914 3RD ST. |
| CONT: TREND WEST INC. |
| TEL: 561-358-8817 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: THURS. JULY 21 /16 |
| ACTION: DENIED |
| |
| 1) SHEET S1: |
| |
| 1A) 2ND REQUEST. THIS SHEET AND THE ELECTRICAL SHEETS |
| SHOW 5 DWELLING UNITS, BUT THE DESIGNER OF RECORD MAKE |
| NUMEROUS MENTION TO THE2014 RESIDENTIAL CODE. PLEASE |
| NOTE THE FBC- RESIDENTIAL CODE IS FOR 1 & 2 FAMILY |
| ONLY!!!!! PLEASE NOTE THIS 5 UNIT RESIDENTIAL STRUCTURE |
| IS COVERED AND TO BE REVIEWED UNDER THE 2014 |
| FBC-BUILDING CODE- BUILDING CODE. PLEASE CORRECT THE |
| CODE REFERENCES TO THE RESIDENTIAL CODE. |
| |
| 1B) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE |
| EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL |
| SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND |
| DOCUMENTS: A FLOOR PLAN MISSING FROM THE 2ND REVIEW. |
| |
| 107.3.5..11 COMMERCIAL BUILDINGS: |
| FLOOR PLAN |
| |
| PLEASE PROVIDE UNDER THE R2 OCCUPANCY WHICH OF THE USES |
| BELOW: |
| APARTMENTS |
| BOARDING HOUSES (NONTRANSIENT) WITH MORE THAN 16 |
| OCCUPANTS |
| CONGREGATE LIVING FACILITIES (NONTRANSIENT) WITH MORE |
| THAN 16 OCCUPANTS |
| HOTELS (NONTRANSIENT) |
| |
| 1C) THERE IS A DISCREPANCY IN THE SCOPE OF WORK BETWEEN |
| THE PERMIT APPLICATION AND THE SHEET S1. SHEET S1 DOES |
| NOT LIST THE REPLACEMENT OF ANY WINDOWS, WHERE AS THE |
| PERMIT APPLICATION DOES INDICATE NEW WINDOWS. NO |
| PRODUCT APPROVALS FOR WINDOWS HAVE BEEN SUBMITTED TO |
| DATE. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. / 2014 |
| FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| PRODUCT APPROVALS: |
| (31)(B) WINDOWS |
| |
| 1D) UNDER COMMENT 1B, THE REQUESTED FLOOR PLAN IS FOR |
| THE REPLACEMENT OF WINDOWS, SHOW SIZES OF WINDOWS FOR |
| ALL ROOMS, USE OF ROOMS, THE EXISITNG WINDOW AND THE |
| TYPE OF PROPOSED WINDOW. PLEASE SHOW COMPLIANCE WITH: |
| 2014 FBC-B: |
| |
| 1D)(1) 1029.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE |
| OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 |
| SQUARE FEET (0.53 M2). |
| EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR GRADEFLOOR |
| EMERGENCY ESCAPE AND RESCUE OPENINGS SHALL BE 5 SQUARE |
| FEET (0.46 M2). |
| |
| 1D)(2) 1029.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET |
| CLEAR OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 |
| MM). THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION |
| SHALL BE 20 INCHES (508 MM). THE NET CLEAR OPENING |
| DIMENSIONS SHALL BE THE RESULT OF NORMAL OPERATION OF |
| THE OPENING. |
| |
| 1D)(3) 1029.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY |
| ESCAPE AND RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE |
| CLEAR OPENING NOT GREATER THAN 44 INCHES (1118 MM) |
| MEASURED FROM THE FLOOR. |
| |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| DEVELOPMENT SERVICES DEPARTMENT |