2016-04-28 19:35:54 | JOB PERMIT NUMBER: 16041147 |
| JOB ADDRESS: 914 3RD ST 1 |
| WEST PALM BEACH FLORIDA |
| DATE: APRIL 28 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - ELECTRICAL SERVICE RISER SHOWS 2? CONDUIT WITH 2 SETS |
| OF 3/0 AWG IN PARALLEL , HOWEVER TABLE ANNEX C CONDUIT |
| FILL STATES ONLY 5 WIRES FIT ASSUMING EITHER IMC OR RMC |
| IS BEING INSTALLED. CLARIFY AND CORRECT ACCORDINGLY ? |
| - PROVIDE INTERSYSTEM BONDING TERMINAL STRIP ON THE |
| GROUNDING DETAIL IN THE RISER DIAGRAM. NEC 250.94 |
| - ELECTRICAL NOTE OF LIGHTING NEEDING TO BE 50 % HIGH |
| EFFICIENT IS INCORRECT FBC-E R 404.1 A MINIMUM 75 % |
| LAMPS SHALL BE HIGH EFFICACY , FURTHER MORE CHANGE THE |
| CODE REFERENCE OF NEC 2008 TO THE APPLICABLE 2011 IN |
| TAMPER RESISTANT RECEPTACLE NOTE. |
| - SERVICE EQUIPMENT TO INCLUDE ALL PERMANENT PLAQUES OF |
| NEC 225.37 , INTERIOR PANELBOARDS TO HAVE |
| IDENTIFICATION OF SOURCE OF SUPPLY IN ACCORDANCE WITH |
| NEC 408.4 (B) |
| - FOR FINAL INSPECTION ARC-FLASH HAZARD WARNING LABELS |
| AND AVAILABLE FAULT CURRENT MARKINGS MUST BE ON |
| ELECTRICAL APPARATUS SUITABLE TO WITHSTAND ENVIRONMENT. |
| - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY |
| WITH NEC 300.21 AND FBC SECTION 714. ANY FIRE RATED |
| STRUCTURE THAT IS COMPROMISED SHALL BE RETURNED TO ITS |
| ORIGINAL FIRE-RATING WITH APPROVED FIRE SEALING |
| MATERIAL. |
| - PROVIDE SPECS ON A/C WALL UNITS TO VERIFY IF THEY |
| PROVIDE HEAT PER FBC-R 303.9 EVERY DWELLING UNIT |
| HABITABLE ROOM SHALL BE CAPABLE OF MAINTAINING 68 |
| DEGREES FAHRENHEIT AT 3 FT ABOVE FLOOR AND 2 FT FROM |
| EXTERIOR WALLS. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |