 DATE: APRIL 28 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - ELECTRICAL SERVICE RISER SHOWS 2? CONDUIT WITH 2 SETS
 OF 3/0 AWG IN PARALLEL , HOWEVER TABLE ANNEX C CONDUIT
 FILL STATES ONLY 5 WIRES FIT ASSUMING EITHER IMC OR RMC
 IS BEING INSTALLED. CLARIFY AND CORRECT ACCORDINGLY ?
 - PROVIDE INTERSYSTEM BONDING TERMINAL STRIP ON THE
 GROUNDING DETAIL IN THE RISER DIAGRAM. NEC 250.94
 - ELECTRICAL NOTE OF LIGHTING NEEDING TO BE 50 % HIGH
 EFFICIENT IS INCORRECT FBC-E R 404.1 A MINIMUM 75 %
 LAMPS SHALL BE HIGH EFFICACY , FURTHER MORE CHANGE THE
 CODE REFERENCE OF NEC 2008 TO THE APPLICABLE 2011 IN
 TAMPER RESISTANT RECEPTACLE NOTE.
 - SERVICE EQUIPMENT TO INCLUDE ALL PERMANENT PLAQUES OF
 NEC 225.37 , INTERIOR PANELBOARDS TO HAVE
 IDENTIFICATION OF SOURCE OF SUPPLY IN ACCORDANCE WITH
 NEC 408.4 (B)
 - FOR FINAL INSPECTION ARC-FLASH HAZARD WARNING LABELS
 AND AVAILABLE FAULT CURRENT MARKINGS MUST BE ON
 ELECTRICAL APPARATUS SUITABLE TO WITHSTAND ENVIRONMENT.
 - ALL ELECTRICAL BOXES IN A DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 AND FBC SECTION 714. ANY FIRE RATED
 STRUCTURE THAT IS COMPROMISED SHALL BE RETURNED TO ITS
 ORIGINAL FIRE-RATING WITH APPROVED FIRE SEALING
 MATERIAL.
 - PROVIDE SPECS ON A/C WALL UNITS TO VERIFY IF THEY
 PROVIDE HEAT PER FBC-R 303.9 EVERY DWELLING UNIT
 HABITABLE ROOM SHALL BE CAPABLE OF MAINTAINING 68
 DEGREES FAHRENHEIT AT 3 FT ABOVE FLOOR AND 2 FT FROM
 EXTERIOR WALLS.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011