2016-04-27 19:07:34PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 ELECTRICAL
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE NO APPROVED ELECTRICAL PLANS FOR THIS
 PROJECT AND NO ELECTRICAL PERMIT HAS BEEN ISSUED.
 THEREFORE, THIS CAN NOT BE AN ELECTRICAL REVISION. A
 SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED.
 FBC 105.1 NOTE: THIS REVISION AND FEES CAN BE APPLIED
 TO THE ELECTRICAL PERMIT APPLICATION.
  
 2) SUBMIT TWO SETS OF ELECTRICAL PLANS WITH THE PRINTED
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 3) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS.
  
 4) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE.
  
 5) FBC- 107.3.5.3 - PROVIDE SMOKE ALARMS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. SMOKE
 ALARMS ARE ALSO REQUIRED ON EACH ADDITIONAL STORY OF
 THE DWELLING.
 R314.3 LOCATION.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING
 BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL
 SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR
 DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN
 INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE
 ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR
 THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL
 IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL.
 WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE
 INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM
 DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT
 THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE
 ALARMS IN THE INDIVIDUAL UNIT.
  
 6) RECEPTACLES ON COVERED PORCH AND SECOND FLOOR DECK
 SHALL BE LISTED FOR WET LOCATIONS AND GFCI PROTECTED.
 FBCR-E3905.11 AND
 FBCR-E3902.3
  
 7) THE OUTLET BOXES SHALL LISTED AND MARKED BY THE
 MANUFACTURER FOR THE CEILING FAN THAT THEY WILL
 SUPPORT. FBCR-E3905.8
  
  