2016-04-27 19:07:34 | PLAN REVIEW COMMENTS |
| |
| |
| 1ST REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| ELECTRICAL |
| |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THERE ARE NO APPROVED ELECTRICAL PLANS FOR THIS |
| PROJECT AND NO ELECTRICAL PERMIT HAS BEEN ISSUED. |
| THEREFORE, THIS CAN NOT BE AN ELECTRICAL REVISION. A |
| SEPARATE PERMIT, APPLICATION AND REVIEW IS REQUIRED. |
| FBC 105.1 NOTE: THIS REVISION AND FEES CAN BE APPLIED |
| TO THE ELECTRICAL PERMIT APPLICATION. |
| |
| 2) SUBMIT TWO SETS OF ELECTRICAL PLANS WITH THE PRINTED |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. FBC 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED |
| AND DRAWN UPON SUITABLE MATERIAL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| |
| 3) NEC 220.40 - SUBMIT ELECTRICAL LOAD CALCULATIONS. |
| |
| 4) FBC 107.3.5.3 - SUBMIT A PANEL SCHEDULE. |
| |
| 5) FBC- 107.3.5.3 - PROVIDE SMOKE ALARMS PURSUANT TO |
| FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. SMOKE |
| ALARMS ARE ALSO REQUIRED ON EACH ADDITIONAL STORY OF |
| THE DWELLING. |
| R314.3 LOCATION. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| WHEN MORE THAN ONE SMOKE ALARM IS REQUIRED TO BE |
| INSTALLED WITHIN AN INDIVIDUAL DWELLING UNIT THE ALARM |
| DEVICES SHALL BE INTERCONNECTED IN SUCH A MANNER THAT |
| THE ACTUATION OF ONE ALARM WILL ACTIVATE ALL OF THE |
| ALARMS IN THE INDIVIDUAL UNIT. |
| |
| 6) RECEPTACLES ON COVERED PORCH AND SECOND FLOOR DECK |
| SHALL BE LISTED FOR WET LOCATIONS AND GFCI PROTECTED. |
| FBCR-E3905.11 AND |
| FBCR-E3902.3 |
| |
| 7) THE OUTLET BOXES SHALL LISTED AND MARKED BY THE |
| MANUFACTURER FOR THE CEILING FAN THAT THEY WILL |
| SUPPORT. FBCR-E3905.8 |
| |
| |