Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop P
Sequence Number 3
Notes
Date Text
2016-11-08 08:49:353RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW TOILET DISPENSER 7"-9" OFF THE FRONT EDGE OF
 TOILET. PER FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 2. SHOW THE WATER CLOSET 16" MIN AND 18" MAX OFF THE
 SIDE WALL TO CENTERLINE OF TOILET. PER FBC ACC 604.2
 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION
  
 3. THE HORIZONTAL DRY VENT AT THE END OF THE RISER
 DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO VENT
 SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT CONNECTION
 TO DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
 905.4 VERTICAL RISE OF VENT.
 EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT
 LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM
 OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED.
  
 4.THE NOTE ON THE RISER ABOVE THE TOILET READS 11/2" IS
 THIS INDICATING PIPE SIZE WATER CLOSET SHALL BE ON MIN
 OF 3" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. IF THE TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO
 THE HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. THE THREE COMPARTMENT SINK AND THE DISH WASHER SHALL
 BE INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL
 DISHWASHING MACHINES.
 THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE
 SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A
 STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION
 802.2.
 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS.
 SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF
 UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN
 THE PREPARATION, SERVING OR EATING OF FOOD SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK
 TO THE DRAINAGE SYSTEM.
  
  