2016-11-08 08:49:35 | 3RD REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW TOILET DISPENSER 7"-9" OFF THE FRONT EDGE OF |
| TOILET. PER FBC ACC 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL |
| NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES |
| NOT ALLOW CONTINUOUS PAPER FLOW. |
| |
| 2. SHOW THE WATER CLOSET 16" MIN AND 18" MAX OFF THE |
| SIDE WALL TO CENTERLINE OF TOILET. PER FBC ACC 604.2 |
| LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION |
| |
| 3. THE HORIZONTAL DRY VENT AT THE END OF THE RISER |
| DIAGRAM IS NOT ALLOWED AND IS NOT REQUIRED TO VENT |
| SYSTEM PLEASE REMOVE. PER FBC PL 905.3 VENT CONNECTION |
| TO DRAINAGE SYSTEM. |
| EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| PIPE. |
| 905.4 VERTICAL RISE OF VENT. |
| EVERY DRY VENT SHALL RISE VERTICALLY TO A POINT NOT |
| LESS THAN 6 INCHES (152 MM) ABOVE THE FLOOD LEVEL RIM |
| OF THE HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED. |
| |
| 4.THE NOTE ON THE RISER ABOVE THE TOILET READS 11/2" IS |
| THIS INDICATING PIPE SIZE WATER CLOSET SHALL BE ON MIN |
| OF 3" PIPE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. IF THE TOILET IS A FLOOR MOUNT IT SHOULD CONNECT TO |
| THE HORIZONTAL RUN OF DRAIN PLEASE CLARIFY. PER WPB |
| AMEND TO FBC 107.2.1 |
| |
| 6. THE THREE COMPARTMENT SINK AND THE DISH WASHER SHALL |
| BE INDIRECTLY WASTED. PER FBC PL 802.1.7 COMMERCIAL |
| DISHWASHING MACHINES. |
| THE DISCHARGE FROM A COMMERCIAL DISHWASHING MACHINE |
| SHALL BE THROUGH AN AIR GAP OR AIR BREAK INTO A |
| STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH SECTION |
| 802.2. |
| 802.1.8 FOOD UTENSILS, DISHES, POTS AND PANS SINKS. |
| SINKS USED FOR THE WASHING, RINSING OR SANITIZING OF |
| UTENSILS, DISHES, POTS, PANS OR SERVICE WARE USED IN |
| THE PREPARATION, SERVING OR EATING OF FOOD SHALL |
| DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AN AIR BREAK |
| TO THE DRAINAGE SYSTEM. |
| |
| |