2016-07-31 09:43:38 | 1) SHT. 2 - THE TOILET PAPER DISPENSER SHALL COMPLY | | WITH FBC-ACCESS.SEC.604.9.6. | | 2) THE GRAB BARS SHALL BE INSTALLED IN ACCORDANCE WITH | | FBC-ACCESS. SEC. 609.4. | | 3) THE WATER CLOSET SHALL BE PROVIDED WITH A CLEAR | | FLOOR SPACE OF 60 INCHES WIDE BY 56 INCHES DEEP IN | | ACCORDANCE WITH 2014 FBC-ACCESS SEC.604.3.1, 604.3.2. | | AS DESIIGNED, THE TOILET ROOM IS NOT WIDE ENOUGH. | | 4) THE SANITARY RISERS DO COMPLY WITH THE | | FBC-PLUMBING.FIXTURES ARE NOT VENTED, FLAT,DRY VENTS | | NOT PERRMITTED BY CODE, NO CLEANOUTS IN STACKS. 2014 | | FBC-PLUMBING SECS.905.3,901.2.1, 708.3.4. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|