2016-07-31 09:43:381) SHT. 2 - THE TOILET PAPER DISPENSER SHALL COMPLY
 WITH FBC-ACCESS.SEC.604.9.6.
 2) THE GRAB BARS SHALL BE INSTALLED IN ACCORDANCE WITH
 FBC-ACCESS. SEC. 609.4.
 3) THE WATER CLOSET SHALL BE PROVIDED WITH A CLEAR
 FLOOR SPACE OF 60 INCHES WIDE BY 56 INCHES DEEP IN
 ACCORDANCE WITH 2014 FBC-ACCESS SEC.604.3.1, 604.3.2.
 AS DESIIGNED, THE TOILET ROOM IS NOT WIDE ENOUGH.
 4) THE SANITARY RISERS DO COMPLY WITH THE
 FBC-PLUMBING.FIXTURES ARE NOT VENTED, FLAT,DRY VENTS
 NOT PERRMITTED BY CODE, NO CLEANOUTS IN STACKS. 2014
 FBC-PLUMBING SECS.905.3,901.2.1, 708.3.4.
  