2016-07-21 12:50:50 | JOB PERMIT NUMBER: 16041117 |
| JOB ADDRESS: 6611 SOUTH DIXIE HIGHWAY |
| WEST PALM BEACH FLORIDA "LOS ALTOS DE JALISCO" ( |
| EXISTING RESTAURANT ) |
| DATE: JULY 21 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - QUAD RECEPTACLES IN SMOOTHIE JUICE BAR PREP AREA |
| SHALL HAVE GFCI PROTECTION NEC 210.8(B) |
| - EMERGENCY LIGHTING WAS SHOWN IN THE KITCHEN, HOWEVER |
| PLEASE CORRECT THE NOTE TO STATE THAT EXIT / EMERGENCY |
| LIGHTS SHALL BE CONNECTED TO THE LOCAL LIGHTING AHEAD |
| SERVED BY AREA. NEC 700.12(F)(4) |
| - OCCUPANCY SENSOR IN BATH WAS NOT ADDED AS REQUESTED |
| PLEASE COMPLY WITH FBC E SECTION C405.2.2.2. IN |
| ADDITION ALL DEVICES IN THE ADA BATHROOM SHALL BE IN |
| COMPLIANCE WITH OBSTRUCTED & UNOBSTRUCTED FORWARD REACH |
| REQUIREMENTS 48?? HIGH SIDE AND 15?? LOW SIDE ABOVE THE |
| FINISH FLOOR. FBC A SECTION 308 ( VERIFY DEPTH IF |
| APPLICABLE ) |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. |
| ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 561-805-6713 |
| |