Plan Review Notes
Plan Review Notes For Permit 16041117
Permit Number 16041117
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-04-27 14:41:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET 1 OF 3 - THERE IS NO REFERENCE OF COMPLIANCE
 WITH THE CURRENT FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011
 EDITION.
  
 2) SHEET 1 OF 3 - COMMENT # 10 INDICATES A REFERENCE TO
 NEW GAS SERVICE. ALL GAS SERVICE WORK SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS.
  
 3) SHEET 1 OF 3 - NO OCCUPANCY CLASSIFICATION, OCCUPANY
 LOAD, OR LIFE SAFETY PLAN IS PROVIDED. PLEASE PROVIDE
 IN COMPLAINCE WITH THE ABOVE REFERENCED FIRE CODES.
  
 4) SHEET 3 OF 3 - THERE IS A NOTE INDICATING THE
 DIMENSION OF A HOOD. COMMERCIAL COOKING EQUIPMENT SHALL
 COMPLY WITH NFPA 96, 2011 EDITION. THE HOOD SHALL
 EXTEND TO OVER ALL COOKING EQUIPMENT INCLUDING THE DEEP
 FRYER AND GAS GRILL. THE HOOD SYSTEM WORK SHALL BE
 SUBMITTED AND COMPLETED UNDER SEPARATE SHOP DRAWING.
  
 5) SHEET 3 OF 3 - THERE IS NO INDICATION OF A HOOD
 SUPPRESSION SYSTEM. HOOD FIRE PROTECTION SHALL BE
 PROVIDED FOR IN COMPLIANCE WITH NFPA 96 AND APPLICABLE
 CODES UNDER SEPARATE SHOP DRAWINGS.
  
 6) SHEET 3 OF 3 - THERE IS NO INDICATION OF ANY FIRE
 EXTINGUISHERS, INCLUDING ONE CLASS K FOR THE DEEP FAT
 FYER. PLEASE PROVIDE PER NFPA 10.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  