2016-04-27 14:41:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET 1 OF 3 - THERE IS NO REFERENCE OF COMPLIANCE |
| WITH THE CURRENT FIRE CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012 |
| EDITION. |
| COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2011 |
| EDITION. |
| |
| 2) SHEET 1 OF 3 - COMMENT # 10 INDICATES A REFERENCE TO |
| NEW GAS SERVICE. ALL GAS SERVICE WORK SHALL BE DONE |
| UNDER SEPARATE SHOP DRAWINGS. |
| |
| 3) SHEET 1 OF 3 - NO OCCUPANCY CLASSIFICATION, OCCUPANY |
| LOAD, OR LIFE SAFETY PLAN IS PROVIDED. PLEASE PROVIDE |
| IN COMPLAINCE WITH THE ABOVE REFERENCED FIRE CODES. |
| |
| 4) SHEET 3 OF 3 - THERE IS A NOTE INDICATING THE |
| DIMENSION OF A HOOD. COMMERCIAL COOKING EQUIPMENT SHALL |
| COMPLY WITH NFPA 96, 2011 EDITION. THE HOOD SHALL |
| EXTEND TO OVER ALL COOKING EQUIPMENT INCLUDING THE DEEP |
| FRYER AND GAS GRILL. THE HOOD SYSTEM WORK SHALL BE |
| SUBMITTED AND COMPLETED UNDER SEPARATE SHOP DRAWING. |
| |
| 5) SHEET 3 OF 3 - THERE IS NO INDICATION OF A HOOD |
| SUPPRESSION SYSTEM. HOOD FIRE PROTECTION SHALL BE |
| PROVIDED FOR IN COMPLIANCE WITH NFPA 96 AND APPLICABLE |
| CODES UNDER SEPARATE SHOP DRAWINGS. |
| |
| 6) SHEET 3 OF 3 - THERE IS NO INDICATION OF ANY FIRE |
| EXTINGUISHERS, INCLUDING ONE CLASS K FOR THE DEEP FAT |
| FYER. PLEASE PROVIDE PER NFPA 10. |
| |
| PETER LEDUC |
| FIRE MARSHAL |