2016-05-09 09:07:49REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - LOW VOLTAGE AND FIRE ALARM SHALL BE UNDER A SEPERATE
 PERMIT WITH SEPERATE DRAWINGS.
  
 - SHEET E02.02, NO EMERGENCY LIGHTING SHOWN ? FBC
 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. THE MEANS
 OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE
 ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY
 THE MEANS OF EGRESS ARE OCCUPIED.FBC-B 1006.2.
 EMERGENCY LIGHTING IS REQUIRED
 EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF
 SAME LOCAL AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY
 THE AREA, EM LIGHTS MAY BE ON OWN CIRCUIT. NEC 700.12
 (F) (4)