Plan Review Notes For Permit 16041109 |
Permit Number |
16041109 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-05-09 09:07:49 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - LOW VOLTAGE AND FIRE ALARM SHALL BE UNDER A SEPERATE | | PERMIT WITH SEPERATE DRAWINGS. | | | | - SHEET E02.02, NO EMERGENCY LIGHTING SHOWN ? FBC | | 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED. THE MEANS | | OF EGRESS, INCLUDING THE EXIT DISCHARGE, SHALL BE | | ILLUMINATED AT ALL TIMES THE BUILDING SPACE SERVED BY | | THE MEANS OF EGRESS ARE OCCUPIED.FBC-B 1006.2. | | EMERGENCY LIGHTING IS REQUIRED | | EMERGENCY LIGHTING SHALL BE FED BY LIGHTING CIRCUIT OF | | SAME LOCAL AREA. *IF 3 OR MORE LIGHTING CIRCUITS SUPPLY | | THE AREA, EM LIGHTS MAY BE ON OWN CIRCUIT. NEC 700.12 | | (F) (4) |
|