Plan Review Notes
Plan Review Notes For Permit 16040987
Permit Number 16040987
Review Stop B
Sequence Number 2
Notes
Date Text
2016-06-22 11:02:20 
 BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 DATE: 6/22/16
 ACTION: DENIED
  
 1. ALL PROPOSED DOORS ARE TO BE INSTALLED IN RATED
 CORRIDORS. PROVIDE DOCUMENTATION THAT DOORS WILL COMPLY
 WITH THE FOLLOWING REQUIREMENTS:
  
 716.5.3 DOOR ASSEMBLIES IN CORRIDORS AND SMOKE
 BARRIERS.
 FIRE DOOR ASSEMBLIES REQUIRED TO HAVE A MINIMUM FIRE
 PROTECTION RATING OF 20 MINUTES WHERE LOCATED IN
 CORRIDOR WALLS OR SMOKE BARRIER WALLS HAVING A
 FIRE-RESISTANCE RATING IN ACCORDANCE WITH TABLE 716.5
 SHALL BE TESTED IN ACCORDANCE WITH NFPA 252 OR UL 10C
 WITHOUT THE HOSE STREAM TEST.
  
 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES.
 APPROVED FIRE DOOR AND FIRE SHUTTER ASSEMBLIES SHALL BE
 CONSTRUCTED OF ANY MATERIAL OR ASSEMBLY OF COMPONENT
 MATERIALS THAT CONFORMS TO THE TEST REQUIREMENTS OF
 SECTION 716.5.1, 716.5.2 OR 716.5.3 AND THE FIRE
 PROTECTION RATING INDICATED IN TABLE 716.5. FIRE DOOR
 FRAMES WITH TRANSOM LIGHTS, SIDELIGHTS OR BOTH SHALL BE
 PERMITTED IN ACCORDANCE WITH SECTION 716.5.6. FIRE DOOR
 ASSEMBLIES AND SHUTTERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND NFPA
 80.
  
 716.5.7.1 FIRE DOOR LABELING REQUIREMENTS.
 FIRE DOORS SHALL BE LABELED SHOWING THE NAME OF THE
 MANUFACTURER OR OTHER IDENTIFICATION READILY TRACEABLE
 BACK TO THE MANUFACTURER, THE NAME OR TRADEMARK OF THE
 THIRD PARTY INSPECTION AGENCY, THE FIRE PROTECTION
 RATING AND, WHERE REQUIRED FOR FIRE DOORS IN INTERIOR
 EXIT STAIRWAYS AND RAMPS AND EXIT PASSAGEWAYS BY
 SECTION 716.5.5, THE MAXIMUM TRANSMITTED TEMPERATURE
 END POINT. SMOKE AND DRAFT CONTROL DOORS COMPLYING WITH
 UL 1784 SHALL BE LABELED AS SUCH AND SHALL ALSO COMPLY
 WITH SECTION 716.5.7.3. LABELS SHALL BE APPROVED AND
 PERMANENTLY AFFIXED. THE LABEL SHALL BE APPLIED AT THE
 FACTORY OR LOCATION WHERE FABRICATION AND ASSEMBLY ARE
 PERFORMED.
  
 2. COMPLY WITH FIRE REVIEW COMMENTS.
  