Plan Review Notes
Plan Review Notes For Permit 16040987
Permit Number 16040987
Review Stop B
Sequence Number 1
Notes
Date Text
2016-05-04 14:35:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NO INFORMATION PROVIDED. PLAN SHOULD INCLUDE
 INFORMATION TO DETERMINE CODE COMPLIANCE. ONLY A
 PRODUCT APPROVAL WAS SUBMITTED FOR A $30,000 DOOR
 REPLACEMENT JOB IN A HIGH RISE.
  
 FBC 107, PROVIDE ENOUGH INFORMATION FOR A REVIEW TO BE
 PERFORMED. AS I HAVE NO INFORMATION REGARDING WHERE THE
 DOORS WILL BE INSTALLED, I CANNOT DETERMINE WHAT
 INFORMATION IS REQUIRED. SOME INFORMATION YOU MAY WANT
 TO CONSIDER PROVIDING:
  
 THRESHOLD INFORMATION (FBC 2014 ACCESSIBILITY)
 PANIC BAR INFO (FBC 2014 1008)
 A PLAN SHOWING LOCATION OF PROPOSED DOOR REPLACEMENT
 (FBC 107)
 BUILDING HEIGHT (ENGINEERING IS REQUIRED FOR BUILDINGS
 OVER 60', FBC 1609)
 IF PANIC BARS ARE NOT PROVIDED, THE PLAN SHOULD SHOW
 WHY IT IS NOT REQUIRED AT THAT LOCATION
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
  
  