Plan Review Notes
Plan Review Notes For Permit 16040973
Permit Number 16040973
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-27 11:07:16REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 NEC 240.21 C(1) , NEC 240.21 C(4) TRANSFORMER SECONDARY
 CONDUCTORS MUST TERMINATE TO A OVERCURRENT PROTECTION
 DEVICE. REFERENCE TABLE NEC 450.3 (B)
 NEC 240.21 B(5) FEEDER TAP CONDUCTORS MUST BE PROTECTED
 BY A OVERCURRENT PROTECTION. REFERENCE NEC 408.36
 PANELBOARD PROTECTION.
 RISER DIAGRAM SHOWS EQUIPMENT "T1" , "T2" , "TL" AS MLO
 AND PANEL SCHEDULE REFLECTS MCB ? CLARIFY AND RE-ADJUST
 ACCORDINGLY.
  