Plan Review Notes
Plan Review Notes For Permit 16040951
Permit Number 16040951
Review Stop E
Sequence Number 1
Notes
Date Text
2016-05-12 12:32:08REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED
 BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR PROVIDE
 EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS.
  
 NEC 250.94 BONDING FOR OTHER SYSTEMS. THE INTER-SYSTEM
 BONDING TERMINAL PRESCRIBED SHALL BE INSTALLED.
  
 PROVIDE A GROUNDING DETAIL TO THE ELECTRICAL SYSTEM (
 GROUNDING ELECTRODE SYSTEM ) ALTERNATE SOURCE TRANSFER
 EQUIPMENT DOES NOT INCLUDE A SWITCHING ACTION IN THE
 GROUNDED CONDUCTOR AND ALLOWS IT TO REMAIN SOLIDLY
 CONNECTED TO THE
 SERVICE-SUPPLIED GROUNDED CONDUCTOR WHEN THE ALTERNATE
 SOURCE IS OPERATIONAL AND SUPPLYING THE LOAD SERVED.
 WPBA 107
  
 250.35 PERMANENTLY INSTALLED GENERATORS. A CONDUCTOR
 THAT PROVIDES AN EFFECTIVE GROUND-FAULT CURRENT PATH
 SHALL BE INSTALLED WITH THE SUPPLY CONDUCTORS FROM A
 PERMANENTLY INSTALLED GENERATOR.
  
  
  