Notes |
Date |
Text |
2016-05-12 12:32:08 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | NEC 250.56- SERVICE GROUNDING ELECTRODE TO BE AUGMENTED | | BY AN ADDITIONAL ELECTRODE 6FEET AWAY OR PROVIDE | | EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR LESS. | | | | NEC 250.94 BONDING FOR OTHER SYSTEMS. THE INTER-SYSTEM | | BONDING TERMINAL PRESCRIBED SHALL BE INSTALLED. | | | | PROVIDE A GROUNDING DETAIL TO THE ELECTRICAL SYSTEM ( | | GROUNDING ELECTRODE SYSTEM ) ALTERNATE SOURCE TRANSFER | | EQUIPMENT DOES NOT INCLUDE A SWITCHING ACTION IN THE | | GROUNDED CONDUCTOR AND ALLOWS IT TO REMAIN SOLIDLY | | CONNECTED TO THE | | SERVICE-SUPPLIED GROUNDED CONDUCTOR WHEN THE ALTERNATE | | SOURCE IS OPERATIONAL AND SUPPLYING THE LOAD SERVED. | | WPBA 107 | | | | 250.35 PERMANENTLY INSTALLED GENERATORS. A CONDUCTOR | | THAT PROVIDES AN EFFECTIVE GROUND-FAULT CURRENT PATH | | SHALL BE INSTALLED WITH THE SUPPLY CONDUCTORS FROM A | | PERMANENTLY INSTALLED GENERATOR. | | | | | | |
|