2016-11-04 08:21:26 | RESIDENTIAL (R3) FRONT REVISION, SECOND MECHANICAL |
| REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014). |
| |
| NOTE: |
| ENGINEER MAY BE CHARGED A FOUR TIMES THE PLAN REVIEW |
| FEE IF PLANS ARE DENIED 3 TIMES OR MORE. SEE FLORIDA |
| STATUTE 553.80(2)(B). |
| |
| 1- PLANS NEED TO PROVIDE COMPLIANCE WITH THE BALANCED |
| RETURN AIR OF ALL ROOMS AS REQUIRED BY SEC. M1602.4 |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 2- REVISE THE EQUIPMENT SIZING CALCULATIONS. PLANS WERE |
| REVISED TO DISCARD THE ADDITION. EQUIPMENT SIZING |
| CALCULATIONS WERE NOT REVISED. NOTE: CALCULATIONS |
| SUBMITTED ARE DONE USING OLD SOFTWARE. PROVIDE REVISED |
| EQUIPMENT SIZING CALCULATIONS USING CURRENT VERSION OF |
| ENERGYGAUGE SOFTWARE. (OR USE ANY OTHER APPROVED |
| SOFTWARE). PLEASE MAKE SURE CALCULATIONS ARE DONE BASED |
| ON THE ACTUAL ORIENTATION OF THE BUILDING TO AVOID |
| CONFLICTS/DELAYS. SEC. R403.6.1 FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| |
| 3- EQUIPMENT LISTED ON THE A/C PLAN SUBMITTED DOESN'T |
| MATCH EQUIPMENT LISTED IN THE EQUIPMENT SIZING |
| CALCULATIONS. REVISE AS REQUIRED. SEC. R403.6.1 |
| FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| REPEAT COMMENT. NOT ADDRESSED. |
| |
| 4- A/C PLAN SUBMITTED SHOWS A/C CONDENSER UNIT ON TOP |
| OF THE FLAT ROOF. PACKAGE UNIT MOUNTING DETAIL PROVIDED |
| DOESN'T APPLY TO UNITS MOUNTED ON A FLAT ROOF. PROVIDE |
| COMPLETE DETAILS AND SPECIFICATIONS FOR THE PROPOSED |
| MOUNTING LOCATION. SEC. R301.1 FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| NOTE: PROVIDE AHRI SHEETS FOR FINAL INSPECTION. |
| |
| |
| ****ENGINEER TO PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ****PLEASE INSERT ANY REVISED SHEET AND REMOVE OLD |
| SHEET. DON'T STAPLE OLD DRAWINGS TO NEW SET. SUBMITT |
| OLD DRAWINGS FOR REFERENCE. |
| |