2016-04-28 16:40:25 | JOB PERMIT NUMBER: 16040905 |
| JOB ADDRESS: 3301 N FLAGLER DR |
| WEST PALM BEACH FLORIDA 33407 |
| DATE: APRIL 28 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. |
| - NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. |
| - SMOKE ALARMS REQUIRED PER RESIDENTIAL CODE SECTIONS |
| 314 & 315. |
| - EXTERIOR DOORS BY TV ROOM AND KITCHEN ARE MISSING A |
| SWITCHED LIGHTING OUTLET ACCORDING TO NEC 210.70 A (2) |
| (B) |
| - PROVIDE AN INTERSYSTEM BONDING STRIP TERMINAL , ADD |
| TO GROUNDING DETAIL IN RISER DIAGRAM. NEC 250.94 |
| - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, |
| SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET |
| SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE |
| SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE |
| LOCATED WITHIN 25 FT. OF THE EQUIPMENT. |
| - MAKE SURE NEW SERVICE LOCATION SHALL COMPLY WITH NEC |
| TABLE 680.8 POOL OVERHEAD CONDUCTORS CLEARANCES. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |
| MARIO VALDES |
| ELECTRICAL PLAN EXAMINER |
| 516-805-6713 |
| [email protected] |
| |