Plan Review Notes
Plan Review Notes For Permit 16040904
Permit Number 16040904
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-04-28 15:54:53THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLANS ARE NOT IN AGREEMENT WITH ONES
 SUBMITTED WITH THE ENGINEER OF RECORD. PERMIT #
 15091225.
  
 PROVIDE A NOTE OR REVIEW THAT THE SUBMITTED SHOP
 DRAWINGS ARE IN COMPLIANCE/AGREEMENT WITH THE ABOVE
 PERMIT AND ENGINEER OF RECORD.
  
 I AM REQUESTING/NOT REQUIRING A REVIEW STAMP OR LETTER
 FROM THE ENGINEER OF RECORD TO ENSURE AGREEMENT WITH
 THE ABOVE MASTER PERMIT SET.
  
 2) THE SUBMITTED PLANS ONLY SHOW TWO FLOORS OF
 SPRINKLER DRAWINGS. THE BUILDING IS FOUR FLOORS. THESE
 PLANS ARE INCOMPLETE AND A DETAILED REVIEW WAS NOT
 COMPLETED.
  
 PROVIDE A COMPLETE SET OF DRAWINGS REFLECTING AGREEMENT
 WITH NUMBER 1 ABOVE.
  
 3) BASED ON THE ABOVE, THE HYDRAULIC CALCULATIONS MAY
 NEED ADJUSTMENT/RESUBMITTAL.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON RESUBMITTAL
 OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  