2016-04-28 15:54:53 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE SUBMITTED PLANS ARE NOT IN AGREEMENT WITH ONES | | SUBMITTED WITH THE ENGINEER OF RECORD. PERMIT # | | 15091225. | | | | PROVIDE A NOTE OR REVIEW THAT THE SUBMITTED SHOP | | DRAWINGS ARE IN COMPLIANCE/AGREEMENT WITH THE ABOVE | | PERMIT AND ENGINEER OF RECORD. | | | | I AM REQUESTING/NOT REQUIRING A REVIEW STAMP OR LETTER | | FROM THE ENGINEER OF RECORD TO ENSURE AGREEMENT WITH | | THE ABOVE MASTER PERMIT SET. | | | | 2) THE SUBMITTED PLANS ONLY SHOW TWO FLOORS OF | | SPRINKLER DRAWINGS. THE BUILDING IS FOUR FLOORS. THESE | | PLANS ARE INCOMPLETE AND A DETAILED REVIEW WAS NOT | | COMPLETED. | | | | PROVIDE A COMPLETE SET OF DRAWINGS REFLECTING AGREEMENT | | WITH NUMBER 1 ABOVE. | | | | 3) BASED ON THE ABOVE, THE HYDRAULIC CALCULATIONS MAY | | NEED ADJUSTMENT/RESUBMITTAL. | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON RESUBMITTAL | | OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | |
|