Plan Review Notes For Permit 16040890 |
Permit Number |
16040890 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-25 17:08:49 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - AFCI PROTECTION REQUIRED PER NEC 210.12 B | | - TAMPER RESISTANT RECEPTACLES REQUIRED PER NEC 406.11 | | - MISSING LIGHTING OUTLET FOR ATTIC ESPECIALLY SINCE | | AHU UNIT WILL BE INSTALLED IN THIS SPACE NEC 210.70 3 | | - KITCHEN COUNTER-TOP OUTLET SPACING ALONG THE BREAK OF | | THE SINK IS MISSING ADD A GFCI RECEPTACLE ONTO PLANS. | | NEC 210.52 C 1,4 | | - LIGHTING SHALL BE 75 % HIGH EFFICIENT AS WELL AS IC | | RATED AND SEALED TO NOT COMPROMISE BUILDING THERMAL | | ENVELOPE. ( 2 CFM ) FBC- E R 402.4.4 / 404.1.1 | | - NEC 250.94 PROVIDE AN INTERSYSTEM BONDING TERMINAL | | STRIP IN THE RISER DIAGRAM. | | |
|