Date |
Text |
2016-04-27 12:04:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS NOT INDICATION OF COMPLIANCE WITH ANY FIRE |
| CODE NOTED ON ANY PLAN SHEET. PLEASE PROVIDE NOTE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| |
| 2) THERE IS NO INDICATION OF EXISTING FIRE ALARM OR |
| FIRE SPRINKLER SYSTEMS. PLEASE PROVIDE NOTE. |
| |
| IF EITHER SYSTEM IS EXISTING. |
| |
| THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE |
| FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND |
| COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF WALLS |
| REQUIRE AN EVALUATION BY A CERTIFIED LIFE SAFTEY |
| CONTRACTOR. |
| THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| CONSTRUCTION PERIOD. |
| ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| AND COMPLETE PROTECTION IS RETURNED. |
| |
| 3) THERE IS NO INDICATION OR LOCATION OF ANY EXISTING |
| OR NEW SMOKE DETECTION/ALARMS. PLEASE PROVIDE |
| INCOMPLIANCE WITH THE ABOVE NOTED CODES. |
| |
| PETER LEDUC |
| FIRE MARSHAL |