2016-04-22 11:21:25RESIDENTIAL (R3) MECHANICAL REVISION COMMENTS.
 CODE: FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 1- TRANSFER GRILL SIZE SHOWN ON PLAN FOR ALL THE SECOND
 FLOOR BEDROOMS DOESN'T T COMPLY WITH EXCEPTION #2 OF
 SEC. M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 (NOTE: ORIGINAL APPROVED PLAN SPECIFIED 10" X 14"
 R.T.G. OVER DOOR WHICH WAS COMPLIANT).
  
 2- ORIGINAL PLAN M1.00 WAS SIGNED AND SEALED BY THE
 ENGINEER OF RECORD. RE-SUBMIT PLAN WITH ENGINEER OF
 RECORD TITLE BLOCK AND SIGNED AND SEALED BY THE
 ENGINEER OR RECORD (WILLIAM F. STUHRKE, PHD, PE).
 CHAPTER 471 FLORIDA STATUTE.
  