2016-05-09 17:15:48 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED |
| |
| FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS |
| - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING |
| ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER |
| HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS, |
| PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30 |
| PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE. |
| |
| R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| OTHER APPROVED HEATING AND COOLING CALCULATION |
| METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES |
| NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR |
| FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT |
| EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT |
| INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL |
| VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM |
| EXHAUST SYSTEMS. |
| |
| PROVIDE ENERGY AND HEAT LOAD CALCULATIONS. |
| |
| PROVIDE AHRI. |
| |
| CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| PROVIDE CONDENSER TIE DOWN SCHEDULE. |
| |