2016-05-09 17:01:39JOB PERMIT NUMBER: 16040819
 JOB ADDRESS: 314 ALMERIA RD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 20 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - RISER DIAGRAM GROUNDING DETAIL TO INCLUDE INTERSYSTEM
 BONDING TERMINAL. NEC 250.94
 - PANEL SCHEDULE MISSING BATHROOM CIRCUIT WHICH SHALL
 BE 12 AWG WIRE AND 20 AMP OCPD. NEC 210.11(C)(3)
 - ADD THE FOLLOWING GENERAL ELECTRICAL NOTES , TAMPER
 RESISTANT RECEPTACLES NEC 406.11 , AND AFCI PROTECTION
 PER NEC 210.12(B)
 - FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN
 10 FEET OF EACH SLEEPING ROOM.
 - RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT , AS
 WELL AS IC RATED AND SEALED TO NOT COMPROMISE BUILDING
 THERMAL ENVELOPE. ( 2 CFM ) FBC-ER 404.1.1 / 402.4.4
 - SWITCHES SHALL HAVE A GROUNDED CONDUCTOR AT THE
 SWITCH LOCATION IN ACCORDANCE WITH NEC 404.2(C)
 - NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, PANELBOARDS.
 - SHOW A/C HANDLER AND COMPRESSOR UNITS ON FLOOR PLANS
 SHOWING DISCONNECTING MEANS. WPBA 107
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011