2016-07-27 14:31:15NEW SINGLE FAMILY RESIDENCE (R3), SECOND BUILDING
 REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 ****NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH "PROVISO" ONCE THE
 ENERGY CALCULATIONS COMMENTS ARE ADDRESSED. PERMIT MAY
 BE ISSUED AND REQUIRED INFORMATION MAY BE SUBMITTED
 LATER PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR
 DELAYS. FEES MAY APPLY. CONTRACTOR TO ADVICE IF PROVISO
 OPTION IS REQUESTED AT THIS TIME OR IF RE-SUBMITTING
 REQUIRED INFORMATION BEFORE ISSUING THE PERMIT.
  
  
 ORIGINAL COMMENT:
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FESS ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
 RESPONSE:
 PLANS SUBMITED HAVE THE PBC STAMP (MU-2016-16556). BUT
 SUBMITTAL IS MISSING THE COPY OF THE PAID RECEIPT.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) OWNER/AGENT TO CERTIFY AND DATE THE ENERGY
 CALCULATIONS AT THE BOTTOM OF THE FORM AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). NOTE: BOTH FORMS MAIN HOUSE AND
 GARAGE/APARTMENT.
  
 B) CONTRACTOR TO COMPLETE THE EPL DISPLAY CARD AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014). NOTE: BOTH FORMS MAIN HOUSE AND
 GARAGE/APARTMENT.
  
 C) COMPLETE THE INSPECTION COMPONENT CRITERIA TABLE
 402.4.1.1 SUBMITTED. SEC. R405.4.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). NOTE: BOTH FORMS MAIN
 HOUSE AND GARAGE/APARTMENT.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) ARCHED ENTRY DOOR AS SHOWN ON PLANS.
 RESPONSE:
 USE OF EXISTING HISTORIC ENTRY DOOR WAS APPROVED BY
 ROBERT BROWN (BUILDING OFFICIAL). THE DOOR STILL NEEDS
 TO COMPLY WITH THE PRODUCT APPROVAL REQUIREMENT. THIS
 MAY BE ACCOMPLISHED BY APPLYING FOR ONE TIME LOCAL
 PRODUCT APPROVAL. PROVIDE COMPLETE ENGINEERING ANALYSIS
 FOR LOCAL PRODUCT APPROVAL TO BE REVIEWED AND APPROVED
 BY THE BUILDING OFFICIAL. PLEASE CONTACT ROBERT BROWN
 FOR SUBMITTAL PACKAGE REQUIREMENTS. NOTE: IF THERE IS
 GLAZING IN THE DOOR, THEN SUBMITT HURRICANE IMPACT
 PROTECTION INFORMATION AT TIME OF ENTRY DOOR LOCAL
 PRODUCT APPROVAL SUBMITTAL.
  
 B) FLAT ROOF NOA 13-1217.01 SUBMITTED:
 (1) SELECTED ASSEMBLY ON PAGE 30 OF 33 IS FOR AN
 NON-INSULATED ROOF SYSTEM. ARCHITECTURAL PLANS CALL FOR
 R-21 MIN. RIGID INSULATION (SEE KEY NOTE #0703 ON
 ARCHITECTURAL PLANS). NEED TO SELECT ASSEMBLY WITH
 RIGID INSULATION AS SPECIFIED BY THE ARCHITECT. NOTE:
 IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED BY GENERAL LIMITATION
 #7. ASSEMBLIES WITH GENERAL LIMITATION #9 DON'T ALLOW
 RAS 117 CALCULATIONS.
  
 ORIGINAL COMMENT:
 C) PRECAST LINTELS AS SHOWN ON PLANS.
 RESPONSE:
 NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 D) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD. (NOTE: DESIGNER OF RECORD NEEDS TO SPECIFY ROOF
 TILE FASTENING. SEE ITEM # 5 BELOW).
 RESPONSE:
 (1) NOA 12-0529.01 SUBMITTED EXPIRED ON 01/03/16. NEED
 CURRENT NOA.
 (2) ROOF TILE ADHESIVE RTA-1 IS NOT LISTED ON THE ROOF
 TILE NOA SUBMITTED. THIS ADHESIVE NEEDS TO BE LISTED ON
 THE ROOF TILE OR COMPLETE PROVIDE COMPLETE PRODUCT
 APPROVAL INFORMATION AND APPLY FOR LOCAL PRODUCT
 APPROVAL FOR PROPOSED INSTALLATION. LOCAL PRODUCT
 APPROVAL TO BE APPROVED BY THE BUILDING OFFICIAL.
  
 ORIGINAL COMMENT:
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO VERIFY
 COMPLIANCE WITH THE COMPONENTS AND CLADDING DESIGN
 PRESSURES.
 RESPONSE:
 THE STRUCTURAL ENGINEER OF RECORD IS THE ONE THAT NEEDS
 TO APPROVE THE PRODUCT APPROVALS. PRODUCT APPROVALS ARE
 FOR COMPONENTS AND CLADDING. THAT'S WHY THE STRUCTURAL
 ENGINEER NEEDS TO APPROVE THEM. NOTE: ENGINEER TO
 PROVIDE REVIEW STAMP ON EACH PRODUCT APPROVAL OR TO
 PROVIDE LETTER THAT CLEARLY IDENTIFY EACH PRODUCT
 APPROVAL (NOA OR FLORIDA PRODUCT APPROVAL NUMBER,
 MODEL, ETC,) REVIEW LETTER SUBMITTED BY THE ARCHITECT
 IS NOT ACCEPTABLE BECAUSE IS TOO GENERAL. THERE IS NO
 WAY OF REFERENCING WHICH SPECIFIC PRODUCT APPROVALS
 WERE APPROVED.
  
 ORIGINAL COMMENT:
 5- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN ADHESIVE PRODUCT
 APPROVAL IS REQUIRED. (NOTE: DESIGNER OF RECORD TO
 SPECIFY THE MINIMUM ATTACHMENT RESISTANCE REQUIRED FOR
 THIS BUILDING. SEE NOA 14-0605.03 SUBMITTED FOR
 REFERENCE).
 RESPONSE:
 DESIGNER OF RECORD IS REQUIRED TO SPECIFY SPECIFIC
 FASTENING OPTION. THE PRODUCT APPROVAL IS TO VERIFY
 THAT IT MEETS THE DESIGNER OF RECORD SPECIFICATIONS.
 RESPONSE LETTER STATING "SEE ATTACHED NOA" DOESN'T
 ADDRESS THIS REQUIREMENT.
  
 6- NEW GEOTECHNICAL REPORT SUBMITTED (2 COPIES) NEEDS
 TO HAVE THE ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
  
 IMPORTANT FOR YOUR INFORMATION:
 (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT
 (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR
 DELAYS.
  
 (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION
 OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND
 [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO
 AVOID CONFLICTS OR DELAYS.
  
 (3) PROVIDE PILES SHOP DRAWINGS APPROVED BY THE
 STRUCTURAL ENGINEER OF RECORD.
  
 (4) PLEASE CONTACT/COORDINATE ALL ELEVATIONS
 CERTIFICATES WITH SAMANTHA HILL TO AVOID CONFLICTS OR
 DELAYS AFTER PERMIT IS ISSUED.
 SAMANTHA HILL
 PHONE: 805-6724 EXT: 6724
 E-MAIL: [email protected]
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
 FROM: [email protected] [[email protected]]
 SENT: THURSDAY, JUNE 30, 2016 8:12 PM
 TO: MARTHA BURITICA
 CC: [email protected]; [email protected]; RICK GONZALEZ;
 [email protected]
 SUBJECT: RE: 15040_GREEN RESIDENCE HISTORIC
 RECONSTRUCTION - PERMIT #16040779
  
 MARTHA,
 I HAVE DISCUSSED THE USE OF THE EXISTING DOOR WITH BOTH
 RICK GONZALEZ AND JULIO GOMEZ. I EXPECT THAT YOU GOT
 FEEDBACK FROM THEM. IN CASE YOU DID NOT, PLEASE NOTE
 THAT I TOLD THEM THAT USING THE ORIGINAL DOOR IS OK
 PROVIDED THERE IS AT LEAST ONE OTHER SWING DOOR THAT
 CAN BE USED TO EXIT THE PROPERTY, WITHOUT GOING THROUGH
 A GARAGE. OF COURSE, THAT DOOR MUST MEET THE MINIMUM
 WIDTH REQUIREMENT.
 REGARDS
  
 ROBERT BROWN, CBO
 BUILDING OFFICIAL / BUILDING DIVISION MANAGER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? BUILDING DIVISION
 (561) 805 6652
  