2016-05-25 17:03:07NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FESS ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- A)THIS PROPERTY IS LOCATED IN THE FLOOD ZONE A5. THE
 INFORMATION SHOWN ON THE ELEVATION CERTIFICATE AND
 SURVEY SUBMITTED DON'T MATCH. ELEVATIONS SHOWN ON THE
 ELEVATION CERTIFICATE ARE BASED ON THE NGVD 1929, WHILE
 ELEVATIONS SHOWN ON THE SURVEY ARE BASED ON THE NAVD
 1988. THE FLOOD INSURANCE RATE MAP (FIRM) DATED MARCH
 1, 1979 IS BASED ON NGVD 1929. REVISE ALL THE
 INFORMATION ON THE SURVEY AS REQUIRED USING THE CORRECT
 ELEVATION DATUM. ALSO, COORDINATE INFORMATION WITH THE
 ELEVATION CERTIFICATE PROVIDED.
 CITY ORDINANCE ARTICLE XVII- FLOOD PREVENTION AND
 CONTROL SEC. 94-542.
  
 B) ELEVATION CERTIFICATE SUBMITTED SPECIFIES ATTACHED
 GARAGE. DRAWINGS SUBMITTED SHOW A DETACHED GARAGE.
 REVISE AS REQUIRED TO MATCH PLANS. PROVIDE AN ELEVATION
 CERTIFICATE FOR EACH BUILDING. CITY ORDINANCE ARTICLE
 XVII- FLOOD PREVENTION AND CONTROL SEC. 94-542.
 NOTE: COORDINATE ELEVATION CERTIFICATES WITH SAMANTHA
 HILL AT (561)805-6712 AND [email protected].
  
 3- SHEET S-1:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE AUGER CAST
 PILES "P-1", INCLUDING THE REQUIRED LENGTH. SEC. R301.1
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) TRELLIS DETAIL IS MISSING THE CONNECTION OF 2-2"X8"
 WOOD BEAM TO WOOD POST.. SEC. R301.1 FBC-RESIDENTIAL,
 5TH EDITION (2014).
  
 C) COORDINATE CONCRETE SLAB FINISH ELEVATIONS WITH
 PROPOSED FINISH ELEVATIONS SHOWN ON THE ELEVATION
 CERTIFICATE AND REVISED SURVEY. SEE ITEM # 2(A) ABOVE.
 ALSO, COORDINATE FINISH FLOOR ELEVATION WITH ALL THE
 STRUCTURAL AND ARCHITECTURAL PLANS TO AVOID CONFLICT OR
 DELAYS.
 NOTE: THE GARAGE SLAB IS PITCHED DOWN TO THE FRONT OF
 THE GARAGE. THEREFORE, THE LOWEST FINISH FLOOR
 ELEVATION NEED TO BE INDICATED BY THE GARAGE ENTRANCE.
  
 4- SURVEY SHOWS PROPOSED RETENTION WALLS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL RETENTION WALLS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 5- SHEET S-5:
 A) CLARIFY WHY THE DESIGN PRESSURES FOR THE PRIMARY
 BUILDING AND THE ACCESSORY BUILDING ARE SO DIFFERENT.
 REVISE AS REQUIRED. PROVIDE THE CORRECT DESIGN
 PRESSURES FOR BOTH BUILDINGS ACCORDING TO THE EXPOSURE
 "D", BUILDING HEIGHT, ROOF ZONE AND WALL ZONE (
 INTERIOR OR END). SEC. R301.1 FBC-RESIDENTIAL.
  
 B) UPDATE NOTES FOR THE PRIMARY BUILDING AND THE
 ACCESSORY BUILDING . NOTES REFERENCE SEC. 1609.1.5 OF
 THE 2010 FBC. SPECIFY CURRENT CODE AND SECTION. CHAPTER
 553 FLORIDA STATUTE.
  
 6- ENTRY DOOR SIZE MAY NOT COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R311.2 FBC-RESIDENTIAL. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE 34" WIDE
 DOOR WILL PROVIDE 32" CLEAR WIDTH OPENING.
  
 7- BEDROOM #2 WINDOWS MAY NOT COMPLY WITH THE EGRESS
 REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT THE 30"X64"
 SINGLE HUNG WINDOW WILL PROVIDE 5.7 S.F. CLEAR OPENING.
  
 8- SHEET A-1.02:
 A) REVISE EMERGENCY OVERFLOW NOTE ON THE ROOF STORM
 DRAIN SCHEDULE. THE NOTE READS: "EMERGENCY OVERFLOW
 (EO) AT FROM 2" MAX. ABOVE ROOF LOWEST ELEV.".
 ACCORDING TO SEC. R903.4.1 FBC-RESIDENTIAL THE OVERFLOW
 NEED TO BE "NOT LESS THAN 2 INCHES NOR MORE THAN 4
 INCHES ABOVE THE FINISHED ROOF COVERING AND SHALL BE
 LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND PARAPET SCUPPERS".
 REVISE AS REQUIRED.
  
 B) LOCATION OF THE EMERGENCY OVERFLOW SCUPPERS FOR DECK
 1 AND DECK 2 DON'T COMPLY WITH SEC. R903.4.1
 FBC-RESIDENTIAL. LOCATION TO BE AS CLOSE AS POSSIBLE TO
 THE MAIN SCUPPER. REVISE AS REQUIRED.
  
 9- SPECIFY SIZE AND LOCATION OF ATTIC ACCESS AT MASTER
 BEDROOM AND BEDROOM #1 SHOWING COMPLIANCE WITH SEC.
 R807 FBC-RESIDENTIAL.
  
 10- SHEET A-8.01:
 A) THE WINDERS OF THE FIRST FLOOR AND SECOND FLOOR
 STAIR PLANS NEED TO COMPLY WITH THE 6" MIN. TREAD DEPTH
 AS REQUIRED BY SEC. R311.7.5.2.1 FBC-RESIDENTIAL.
  
 B) REVISE THE WOOD STAIR DETAIL "A". SEE SEC.
 R311.7.5.2 TO SEE HOW THE TREAD IS MEASURED. AND, NEED
 TO ADD THE NOSING AS REQUIRED BY SEC. R311.7.5.2.1
 FBC-RESIDENTIAL. ALSO, UPDATE THE FIRESTOPPING CODE
 SECTION R4409.7.2.3. THIS SECTION APPLIES TO HIGH
 VELOCITY HURRICANE ZONES ONLY.
  
 C) UPDATE THE STAIRS GENERAL NOTES. THE CURRENT CODE IS
 FBC-RESIDENTIAL, 5TH EDITION (2014) NOT FBC 2010. ALSO,
 REFER TO CORRECT SECTION REGARDING FIRESTOPPING . SEC.
 R4409.7.2.3 APPLIES TO HIGH VELOCITY HURRICANE ZONES
 ONLY.
  
 11- SPECIFY DRAFTSTOPPING LOCATION AND MATERIALS ON THE
 SECOND FLOOR FLOOR/CEILING ASSEMBLY AS REQUIRED BY SEC.
 R302.12 FBC-RESIDENTIAL.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE ENERGY CALCULATIONS FOR EACH SEPARATE
 BUILDING: MAIN HOUSE AND GARAGE/APARTMENT. SEC. R101.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. ADDRESS IS INCORRECT.. PROVIDE OWNER'S NAME,
 BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION NUMBER.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) CEILING INSULATION ON ITEM #10 TO MATCH R-VALUE
 SPECIFIED ON PLANS. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 D) CEILING IS NOT VENTED. SEE PLANS. REVIEW ITEM #10 AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 E) FLOOR INFORMATION FOR RAISED FLOOR AND FLOOR OVER
 OTHER SPACE (ABOVE GARAGE) DOESN'T MATCH PLANS. THERE
 IS CONCRETE SLAB ON SECOND FLOOR DECKS (NOT WOOD
 JOISTS) AND THERE IS A CONCRETE SLAB ABOVE THE GARAGE.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) NEED INSULATION BETWEEN GARAGE AND APARTMENT ABOVE.
 SEC. R402.4.1.1 AND TABLE R402.4.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN ENERGY CALCULATIONS ARE NOT USING
 THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 13- ARCHITECTURAL PLANS TO PROVIDE DETAIL AND
 SPECIFICATIONS FOR THE INSULATION IN WALLS, CEILINGS,
 FLOOR BETWEEN GARAGE AND APARTMENT ABOVE. COORDINATE
 WITH THE ENERGY CALCULATIONS TO AVOID CONFLICTS. SEC.
 R103.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 14- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ARCHED ENTRY DOOR AS SHOWN ON PLANS.
  
 B) DOUBLE HUNG WINDOW THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER (+51/-68). FLORIDA PRODUCT
 APPROVAL FL14477-R2 SUBMITTED IS GOOD FOR +/-65PSF.
  
 C) OVERHEAD GARAGE DOORS THAT MEET THE CALCULATED
 DESIGN PRESSURES SHOWN ON PLANS.
  
 D) PITCHED ROOF UNDERLAYMENT. LIMITATION #2 OF THE
 FLORIDA PRODUCT APPROVAL FL17322-R1 SUBMITTED SPECIFIES
 THAT WIND UPLIFT RESISTANCE IS NOT WITHIN THE SCOPE OF
 THIS EVALUATION. NEED TO PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH THE WIND RESISTANCE BASED ON THE
 PROPOSED INSTALLATION. COORDINATE WITH ITEM # 16 BELOW.
 CLEARLY SPECIFY WHICH UNDERLAYMENT IS GOING TO BE USED.
 ALSO, PROVIDE ROOF TILE PRODUCT APPROVAL THAT LISTS
 THIS UNDERLAYMENT..
  
 E) "FLAT ROOF BASE SHEET" NOA 13-1113.05 SUBMITTED IS
 FOR SLOPED ROOFS ONLY. PROVIDE PRODUCT APPROVAL FOR
 FLAT ROOF ASSEMBLIES. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF THE DESIGN PRESSURES OF
 THE SELECTED ASSEMBLY DON'T MEET THE DESIGN PRESSURES
 FOR ALL THE ROOF ZONES.
  
 F) "FLAT ROOF WATERPROOFING" NOA 12-0418.02 SUBMITTED
 IS FOR INSULATED WOOD DECK ASSEMBLIES. THERE ARE NO
 INSULATED WOOD DECK ASSEMBLIES IN THIS PROJECT. PROVIDE
 PRODUCT APPROVAL FOR FLAT ROOF ASSEMBLIES. COORDINATE
 WITH ITEM #14(E) ABOVE. ALSO, REMEMBER THAT THERE ARE
 SOME CONCRETE DECKS SHOWN ON PLANS. PROVIDE PRODUCT
 APPROVAL FOR SUCH ASSEMBLIES.
  
 G) PRECAST LINTELS AS SHOWN ON PLANS.
  
 H) WINDOW MULLIONS AS SHOWN ON PLANS. AND, CLEARLY
 SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES.
  
 I) IPE TILE ROOF DECK PEDESTAL SYSTEM. NEED TO SHOW
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 J) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, SECTIONS AND DETAILS. AND, UPDATE FLORIDA
 PRODUCT APPROVALS LISTED ON THE TRUSS CONNECTOR. NEED
 TO SPECIFY CONNECTORS THAT ARE APPROVED UNDER THE 2014
 CODE VERSION. NUMBERS LISTED ARE FOR AN OLDER CODE.
 PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR OR DESIGNER OF RECORD
 TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 H) ROOF TILE ADHESIVE, IF SPECIFIED BY THE DESIGNER OF
 RECORD.
  
 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO VERIFY
 COMPLIANCE WITH THE COMPONENTS AND CLADDING DESIGN
 PRESSURES.
  
 16- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING
 AS REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ADHESIVE, THEN ADHESIVE PRODUCT
 APPROVAL IS REQUIRED.
  
 17- PROVIDE ICC EVALUATION REPORT FOR THE SPRAY
 INSULATION TO BE USED. AND, DESIGNER OF RECORD TO
 REVIEW AND APPROVE IT PRIOR TO SUBMITTAL TO THIS
 OFFICE. SEC. R316 FBC-RESIDENTIAL.
  
 18- CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR IMPACT
 PROTECTION FOR THE ENTRY DOOR. AND, IF USING THIS
 PRODUCT, THEN PROVIDE COMPLETE INSTALLATION SCHEDULE
 SHOWING PROPOSED INSTALLATION BASED ON THE PRODUCT
 APPROVAL SUBMITTED AND SPECIFIC CONDITION OF THE HOUSE.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 19- PROVIDE COMPLETE INFORMATION FOR THE FACTORY BUILT
 FIREPLACE AND CHIMNEY SHOWING THE LISTING AND LABELING
 IN ACCORDANCE WITH UL 127 AS REQUIRED BY SEC. R1004 AND
 R1005 FBC-RESIDENTIAL.
 AND, DESIGNER OF RECORD TO APPROVE PACKAGE PRIOR TO
 SUBMITTAL.
  
 NOTES:
 (1) ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION. PLEASE COORDINATE WITH SAMANTHA HILL AT
 (561)805-6724 AND [email protected] TO AVOID CONFLICTS OR
 DELAYS.
  
 (2) SPECIAL INSPECTOR IS REQUIRED FOR THE CONSTRUCTION
 OF AUGER CAST PILES. PLEASE COORDINATE WITH KEN CONRAD
 (CHIEF BUILDING INSPECTOR) AT (561)805-6666 AND
 [email protected] FOR APPROVAL OF SPECIAL INSPECTOR TO
 AVOID CONFLICTS OR DELAYS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]