2016-04-28 12:15:42 | ELECTRICAL REVIEW COMMENTS |
| REVIEWED FOR COMPLIANCE WITH: |
| 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 |
| EDITION |
| |
| CORRECTIONS REQUIRED: |
| 1. NEC 404.2(C). WHERE SWITCHES CONTROLLING LIGHTING |
| LOADS SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE |
| GROUNDED BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED |
| LIGHTING CIRCUIT SHALL BE PROVIDED AT THE SWITCH. |
| 2. SHOW FIXED APPLIANCE CIRCUITS ON THE PANEL SCHEDULE |
| AND INCLUDE THEM INTO THE LOAD CALCS. |
| 3. NEC 210.52(E)(1) REQUIRES THAT THERE BE A GFCI |
| PROTECTED OUTLET IN THE FRONT AND REAR OF EVERY |
| DWELLING UNIT WITH GRADE LEVEL ACCESS. |
| 4. NEC 210.52(D) BATHROOMS. IN DWELLING UNITS, AT LEAST |
| ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN BATHROOMS |
| WITHIN 3 FT. OF THE OUTSIDE EDGE OF EACH BASIN. OUTLET |
| IS MISSING IN THE DOWNSTAIRS BATHROOM. |
| 5. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE |
| INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| DISTANCE FROM THE EDGE OF THE WALL. OUTLETS MISSING IN |
| KITCHEN WALL; OUTLET SPACING ON GREAT ROOM WALLS; |
| MASTER BEDROOM; BEDROOM 2; WALL BENEATH ELECTRICAL |
| PANEL, THE GREAT ROOM WALL TO KITCHEN IS 25?; BY CODE |
| IT SHOULD HAVE 3 OUTLETS NOT 2, ALSO CHECK FRONT WALL |
| WHICH HAS 18? BETWEEN OUTLETS. |
| 6. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT. |
| OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THERE ARE |
| OUTLETS MISSING IN THE GREAT ROOM AND BEDROOM 4 |
| 7. PROVIDE MANUFACTURER SPECS FOR THE TANKLESS WATER |
| HEATERS. 13KW IS NOT TO BE PROTECTED OR WIRED AS |
| INDICATED ON PANEL SCHEDULE. CORRECT ACCORDINGLY AND |
| ADJUST LOAD CALCS IF NECESSARY. |
| 8. PER NEC 422.31(B) A DISCONNECT IS REQUIRED FOR THE |
| TANKLESS WATER HEATERS. |
| 9. THE LOAD CALCS AND PANEL SCHEDULE DO NOT MATCH. |
| INCLUDE THE SECOND HVAC UNIT ON PANEL SCHEDULE AND |
| ADJUST THE LOAD CALCS CORRECTLY. |
| 10. NEC 110.33(B) A PERMANENT LADDER OR STAIRWAY SHALL |
| BE PROVIDED TO GIVE SAFE ACCESS TO THE WORKING SPACE |
| AROUND ELECTRICAL EQUIPMENT INSTALLED ON PLATFORMS, |
| BALCONIES, OR MEZZANINE FLOORS OR IN ATTIC OR ROOF |
| ROOMS? SPACES. ELSEWHERE IN THE CODE YOU ARE REQUIRED |
| TO PROVIDE A LIGHT SWITCHED AT THE ENTRANCE TO THE |
| ATTIC THAT ILLUMINATES THE EQUIPMENT IN QUESTION AND A |
| GFI OUTLET WITHIN READY ACCESS. |
| 11. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE |
| SUPPORT OF CEILING FANS SHALL BE MARKED BY THE |
| MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE |
| THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT |
| PADDLE FANS HEAVIER THAN 70 LBS. |
| 12. NEC 410.16(B) PROHIBITS THE USE OF THE TRADITIONAL |
| PORCELAIN PULL CHAIN FIXTURES IN CLOSETS. USE A |
| SUITABLE WALL SWITCHED LUMINARIES. |
| |
| FOR A BETTER UNDERSTANDING OR INDICATION AS TO THE |
| ABOVE COMMENTS, FEEL FREE TO SIGN OUT THE PLAN SET |
| MARKED ?CONTRACTOR?S COPY?. |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |