2016-09-08 10:32:37 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| THESE PROVISO COMMENTS ARE POSTED IN AN EFFORT TO MOVE |
| THIS PROJECT FORWARD. |
| |
| THESE DEFICIENCIES ARE NOTED ON THE 12TH FL WHICH MAY |
| ALLOW AMPLE TIME FOR CONTINUED REVIEW, INFORMATION |
| SHARING AND IF APPLICABLE, SUBMITTED REVISIONS WHILE |
| CONSTRUCTION BEGINS. |
| |
| |
| PREVIOUS COMMENTS: |
| |
| 4) SHEET AS 212A - INDICATES A 48" DOOR IN THE |
| NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300. |
| |
| PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF |
| 48" DOOR AS 240 MAXIMUM. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| NEW COMMENT: |
| |
| THERE ARE TWO LIFE SAFETY PLAN SHEETS FOR THE AMENITY |
| DECK SHEET AS212 & AS 212A. SHEET AS212A SHOWS A HIGHER |
| OCCUPANCY LOAD. ONCE AGAIN WHICH IS THE ACCURATE |
| OCCUPANCY LOAD? IN YOUR RESPONSE YOU CITED AN EXCEPTION |
| FROM |
| THEFBC FOR SHEET AS212A TO ALLOW MORE THROUGH A 48" |
| OPENING. THE FFPC DOES NOT HAVE THAT EXCEPTION. SHOULD |
| AS212A BE THE OCCUPANCY LOAD SHEET BEING THE HIGHER |
| LOAD COUNT THE 48" EXIT IS NON COMPLIANT PER THE FFPC, |
| THE |
| STRICTER REQUIREMENT. |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| 5) SHEET 212A - INDICATES AN 60" WIDE STAIR IN THE |
| NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300. |
| |
| PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF |
| 60" STAIR AS 200 MAXIMUM. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| NEW COMMENT: |
| |
| THERE ARE TWO LIFE SAFETY PLAN SHEETS FOR THE AMENITY |
| DECK SHEET AS212 & AS 212A. SHEET AS212A SHOWS A HIGHER |
| OCCUPANCY LOAD. ONCE AGAIN WHICH IS THE ACCURATE |
| OCCUPANCY LOAD? IN YOUR RESPONSE YOU CITED AN EXCEPTION |
| FROM |
| THEFBC FOR SHEET AS212A TO ALLOW MORE THROUGH A 60" |
| STAIR OPENING. THE FFPC DOES NOT HAVE THAT EXCEPTION. |
| THE HIGHEST LOAD THROUGH A STAIR GREATER THAN 44" IS |
| 225 PER NFPA 101, CHAPTER 7, 7.3.3.2. SHOULD AS212A BE |
| THE |
| OCCUPANCY LOAD SHEET BEING THE HIGHER LOAD COUNT THE |
| 60" EXIT IS NON COMPLIANT PER THE FFPC, THE STRICTER |
| REQUIREMENT. |
| |
| PLEASE REVIEW AND CORRECT |
| |
| |
| |