2016-09-08 10:32:37THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 THESE PROVISO COMMENTS ARE POSTED IN AN EFFORT TO MOVE
 THIS PROJECT FORWARD.
  
 THESE DEFICIENCIES ARE NOTED ON THE 12TH FL WHICH MAY
 ALLOW AMPLE TIME FOR CONTINUED REVIEW, INFORMATION
 SHARING AND IF APPLICABLE, SUBMITTED REVISIONS WHILE
 CONSTRUCTION BEGINS.
  
  
 PREVIOUS COMMENTS:
  
 4) SHEET AS 212A - INDICATES A 48" DOOR IN THE
 NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300.
  
 PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF
 48" DOOR AS 240 MAXIMUM.
  
 PLEASE REVIEW AND CORRECT.
  
  
 NEW COMMENT:
  
 THERE ARE TWO LIFE SAFETY PLAN SHEETS FOR THE AMENITY
 DECK SHEET AS212 & AS 212A. SHEET AS212A SHOWS A HIGHER
 OCCUPANCY LOAD. ONCE AGAIN WHICH IS THE ACCURATE
 OCCUPANCY LOAD? IN YOUR RESPONSE YOU CITED AN EXCEPTION
 FROM
 THEFBC FOR SHEET AS212A TO ALLOW MORE THROUGH A 48"
 OPENING. THE FFPC DOES NOT HAVE THAT EXCEPTION. SHOULD
 AS212A BE THE OCCUPANCY LOAD SHEET BEING THE HIGHER
 LOAD COUNT THE 48" EXIT IS NON COMPLIANT PER THE FFPC,
 THE
 STRICTER REQUIREMENT.
  
 PLEASE REVIEW AND CORRECT
  
  
 5) SHEET 212A - INDICATES AN 60" WIDE STAIR IN THE
 NORTHWEST CORNER WITH AN EXIT CAPACITY OF 300.
  
 PER NFPA 101, CHAPTER 7, INDICATES THE CAPACITY OF OF
 60" STAIR AS 200 MAXIMUM.
  
 PLEASE REVIEW AND CORRECT.
  
  
 NEW COMMENT:
  
 THERE ARE TWO LIFE SAFETY PLAN SHEETS FOR THE AMENITY
 DECK SHEET AS212 & AS 212A. SHEET AS212A SHOWS A HIGHER
 OCCUPANCY LOAD. ONCE AGAIN WHICH IS THE ACCURATE
 OCCUPANCY LOAD? IN YOUR RESPONSE YOU CITED AN EXCEPTION
 FROM
 THEFBC FOR SHEET AS212A TO ALLOW MORE THROUGH A 60"
 STAIR OPENING. THE FFPC DOES NOT HAVE THAT EXCEPTION.
 THE HIGHEST LOAD THROUGH A STAIR GREATER THAN 44" IS
 225 PER NFPA 101, CHAPTER 7, 7.3.3.2. SHOULD AS212A BE
 THE
 OCCUPANCY LOAD SHEET BEING THE HIGHER LOAD COUNT THE
 60" EXIT IS NON COMPLIANT PER THE FFPC, THE STRICTER
 REQUIREMENT.
  
 PLEASE REVIEW AND CORRECT
  
  
  
 PETER LEDUC
 FIRE MARSHAL