2016-07-08 08:54:16 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. AS200, OCCUPANCY SEPARATION REQUIREMENTS, INCIDENTAL |
| USE AREAS, NON PROTECTED SHAFT REFERS TO FBC 2010, |
| PLEASE REVISE AND CHECK ALL. AS201 INCLUDES INFORMATION |
| FROM FBC 2010 (FOR INSTANCE, FBC TABLE 1004.1.1 SHOULD |
| BE 1004.1.2). CHECK ALL CODE REFERENCES NUMBERS, ALL |
| SHEETS, AND UPDATE AS APPLICABLE. |
| |
| 2. ALL SHEETS, POOL DECK OCCUPANT LOAD SHOULD BE |
| CALCULATED AT 15SF GROSS PER PERSON, PLEASE REVISE |
| TABLES AND OCCUPANT LOAD FOR THE POOL DECK. IT DOES NOT |
| APPEAR THAT EXITING IS ADEQUATE FOR THIS ASSEMBLY AREA; |
| FBC 5TH EDITION TABLE 1004.1.2. |
| |
| 3. AS202, DISTANCE BETWEEN EXITS IS SHOWN FOR THE |
| OVERALL BUILDING. PROVIDE DIMENSIONS (DIAGONAL, |
| DISTANCE BETWEEN EXITS) FOR THE PHASED OCCUPANCY, FBC |
| 1015.2.1. CHECK ALL FLOORS, ALL PHASES TO CONFIRM THAT |
| EACH AREA, WHEN OCCUPIED, HAS EXITING IN COMPLIANCE |
| WITH FBC CHAPTER 10. |
| |
| 4. REVISE PLAN TO INCLUDE ACCESSIBLE VAN SPACES IN THE |
| PARKING CALCULATIONS, REVISE PLAN TO SHOW LOCATION OF |
| VAN ACCESSIBLE SPACES, AND CONFIRM AND NOTE HEIGHT |
| CLEARANCE REQUIREMENT ON THE PLAN, FBC 5TH EDITION |
| ACCESSIBILITY 208.2.4, 502.2. |
| |
| 5. THE ACCESSIBLE PARKING SPACE NEAR STAIR 4 DOES NOT |
| HAVE AN ACCESS AISLE IN COMPLIANCE WITH FBC 5TH |
| ACCESSIBILITY FIGURE 502.3. SECTION 502.2 REQUIRES THE |
| ACCESS AISLE TO BE ADJACENT. REVISE AND CHECK ALL. |
| |
| 6. THE PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| PROVISOS: |
| |
| A. PROVISO: TCO AT EACH PHASE IS SUBJECT TO APPROVAL OF |
| THE BUILDING OFFICIAL (OR HIS REPRESENTATIVE) AND FIRE |
| DEPARTMENT, AND MAY INCLUDE ITEMS NOT WITHIN THE SCOPE |
| OF THIS REVIEW. |
| |
| A TCO REQUEST FORM AND FEE WILL BE REQUIRED. THIS FORM |
| IS AVAILABLE UPON REQUEST BY EMAIL. |
| |
| B. PROVISO, LIFE SAFETY PLANS REFER TO LIFE SAFETY |
| SYSTEMS DETAILED ON FMEP SHEETS (LIFE SAFETY TCO NOTES) |
| WHICH HAVE NOT BEEN PROVIDED AT THIS TIME. COMPLIANCE |
| WITH ALL LIFE SAFETY AND ACCESSIBILITY REQUIREMENTS IS |
| REQUIRED FOR EACH PHASE. FMEP SHEETS AND LIFE SAFETY |
| SYSTEM SPECIFICS WILL BE REVIEWED AT TIME OF INTERIOR |
| BUILDOUT PERMIT APPLICATION. |
| |
| C. PROVISO, PERMIT WILL BE ISSUED AT CONTRACTOR'S RISK. |
| FBC105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF |
| THE APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A |
| BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION |
| AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL |
| OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| |
| D. INFORMATIONAL ONLY, A CURSORY REVIEW HAS BEEN |
| PERFORMED ON THE LIFE SAFETY PLAN AND ACCESSIBILITY. |
| DIMENSIONS, DOOR TYPES, HARDWARE SCHEDULE, ETC. IS |
| REQUIRED FOR A COMPREHENSIVE REVIEW WHICH WILL BE |
| PERFORMED AT TIME OF INTERIOR BUILDOUT PERMIT REVIEW. |
| |
| E. PROVISO, THIS STUCTURE SERVES A BUILDING WHICH HAS |
| NOT BEEN REVIEWED BY THIS DEPARTMENT (TRAIN STATION). |
| ACCESSIBLE ROUTE IN COMPLIANCE WITH FBC 5TH EDITION |
| ACCESSIBILITY IS REQUIRED AND WILL BE VERIFIED IN THE |
| FIELD. |
| |
| |
| |
| |