2016-04-18 10:46:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE SUBMITTED PLAN INDICATES A PROPOSED WATER | | CURTAIN ON GLASS WALLS. EACH SECTION OF GLASS WALL HAS | | DOOR THAT OPEN. A WATER CURTAIN IN THIS INSTALLTION IS | | A MISAPPLICATION OF THE CODE AS A WATER CURTAIN CAN NOT | | PROTECT AN OPENING. IT CAN PROTECT FIXED GLASS. | | | | WHAT IS THE INTENT OF THE WATER CURTAIN. IS THE WALL | | REQUIRED TO BE RATED? | | | | PLEASE REVIEW WITH THE ENGINEER OF RECORD. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | | | |
|