Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-04-18 10:46:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLAN INDICATES A PROPOSED WATER
 CURTAIN ON GLASS WALLS. EACH SECTION OF GLASS WALL HAS
 DOOR THAT OPEN. A WATER CURTAIN IN THIS INSTALLTION IS
 A MISAPPLICATION OF THE CODE AS A WATER CURTAIN CAN NOT
 PROTECT AN OPENING. IT CAN PROTECT FIXED GLASS.
  
 WHAT IS THE INTENT OF THE WATER CURTAIN. IS THE WALL
 REQUIRED TO BE RATED?
  
 PLEASE REVIEW WITH THE ENGINEER OF RECORD.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  