Plan Review Notes
Plan Review Notes For Permit 16040667
Permit Number 16040667
Review Stop B
Sequence Number 1
Notes
Date Text
2016-04-18 12:54:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SEE THE ROOF PLAN REVIEW FOR MASTER PERMIT 14120909.
  
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE TO
 BE PROVIDED FOR REVIEW. THE ROOF PERMIT ISSUED IN ERROR
 HAS BEEN VOIDED AND WILL BE REISSUED AFTER REVIEW OF
 THE REQUIRED DOCUMENTS.
  
 FOR YOUR CONVENIENCE, SEE REVIEW FOR 14120909 BELOW:
  
 ****PROVISO****
 ISSUED AT CONTRACTOR?S RISK
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2010 FLORIDA BUILDING CODE WITH 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 NO ROOF COVERING INFORMATION HAS BEEN SUBMITTED AT THIS
 TIME
  
 ROOF PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD,
 ARE TO BE SUBMITTED WITH ROOF PERMIT APPLICATION PRIOR
 TO INSTALLATION
  
 THE ROOF COVERING ASSEMBLY AT THE CONNECTING CORRIDOR
 IS TO HAVE A CLASS B RATING (PER SHEET G101, PER FBC
 706.6 EXCEPTION 3)
  
 ALL ROOFS TO MEET THE FOLLOWING DESIGN PRESSURES PER
 SHEET S8.5:
  
 ZONE 1 +52.0 / -76.4
 ZONE 2 +76.4 / -119.9
 ZONE 3 +52.0 / -119.9
  
  
  
  
  
  