Plan Review Notes For Permit 16040635 |
Permit Number |
16040635 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2016-08-09 11:41:46 | 3RD REVIEW FBC-2014 MECHANICAL | | PERMIT #16040635 | | 8/9/16 | | | | 1) SHEET A1.1: THE AC PLAN IS INCOMPLETE: A) SHOW THE | | RELOCATED DUCT RUNS AND INCLUDE DUCT SIZES. B) INDICATE | | THE SUPPLY AND RETURN CFMS AT EACH NEW OR RELOCATED | | DIFFUSER OR GRILL. | | | | 2) COMMENT #2 FROM THE 1ST REVIEW STILL EXISTS. I HAVE | | RE-PRINTED IT BELOW- PLEASE COMPLY. | | | | REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|