Plan Review Notes
Plan Review Notes For Permit 16040635
Permit Number 16040635
Review Stop M
Sequence Number 2
Notes
Date Text
2016-07-05 12:28:462ND REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING
 PERMIT #16040635
 7/5/16
  
 1) AS PREVIOUSLY REQUESTED, PROVIDE MECHANICAL PLANS.
 THE SUBMITTED RESPONSE NARRATIVE FROM BUTLER
 CONSTRUCTION STATES THAT MECHANICAL PLANS HAVE BEEN
 ATTACHED, AND THERE IS A REFERENCE TO THEM ON SHEET
 A1.0, HOWEVER NO PLANS HAVE BEEN SUBMITTED.
  
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  