2016-07-05 12:28:46 | 2ND REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING | | PERMIT #16040635 | | 7/5/16 | | | | 1) AS PREVIOUSLY REQUESTED, PROVIDE MECHANICAL PLANS. | | THE SUBMITTED RESPONSE NARRATIVE FROM BUTLER | | CONSTRUCTION STATES THAT MECHANICAL PLANS HAVE BEEN | | ATTACHED, AND THERE IS A REFERENCE TO THEM ON SHEET | | A1.0, HOWEVER NO PLANS HAVE BEEN SUBMITTED. | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|