Plan Review Notes For Permit 16040635 |
Permit Number |
16040635 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-07-18 09:24:13 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO'S : | | | | - ADD EXIT/EMERGENCY COMBOS AS RED LINED IN BY FIRE | | REVIEWER FBC 1011 & 1006.2 | | | | - OCCUPANCY SENSORS SHALL BE INSTALLED IN BATHROOMS AS | | WELL AS OFFICES PER FBC E SECTION C405.2.2.2 | | | | - ALL BATHROOMS RECEPTACLE SHALL BE GFCI PROTECTED IN | | ACCORDANCE WITH NEC 210.8(B)(1) |
|