Date |
Text |
2016-04-14 15:41:02 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| 1) PROVIDE AN EXIT SIGN AT THE NEWLY CREATED ACCESS TO |
| THE FRONT EXIT PER NFPA 101, CHAPTER 39 EXISTING |
| BUSINESS OCCUPANCIES AND |
| |
| 39.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| |
| 39.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10. |
| |
| 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| 7.8.1 GENERAL. |
| 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 |
| THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT |
| PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| |
| 7.10.1.2 EXITS. |
| 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| THAT OBVIOUSLY AND CLEARLY ARE IDENTIFIABLE AS EXITS, |
| SHALL BE MARKED BY AN APPROVED SIGN THAT IS READILY |
| VISIBLE FROM ANY DIRECTION OF EXIT ACCESS. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |
| |
| |