2016-04-18 09:57:28 | JOB PERMIT NUMBER: 16040635 |
| JOB ADDRESS: 4807 GEORGIA AVENUE |
| WEST PALM BEACH FLORIDA |
| DATE: APRIL 18 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO |
| THE FRAMING MEMBER BY MECHANICAL MEANS. SUSPENDED |
| CEILING SHALL HAVE ADEQUATE STRENGTH TO ATTACH LIGHTING |
| OR THE LUMINAIRES SHALL BE INDEPENDENTLY SECURED. |
| - ADD A NOTE TO COMPLY WITH FLORIDA BUILDING ENERGY |
| CODE SECTION C 405 MANDATORY LIGHTING CONTROLS. |
| - FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| CONDITIONED & UNCONDITIONED SPACES. |
| - NEC 700.12 (F) (4) - EMERGENCY LIGHTING SHALL BE FED |
| BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR MORE |
| LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY BE ON |
| OWN CIRCUIT. |
| - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY |
| WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| SEALING MATERIALS. |
| - IMPORTANT NOTICE ALL RE ? USED CIRCUITS FOR DIFFERENT |
| APPLICATIONS SHALL BE RE ? IDENTIFIED IN THE PANEL |
| BOARD DIRECTORY. NEC 408.4 A |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |