2016-07-26 15:42:07 | 2ND REVIEW |
| |
| |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHOW COMPLIANCE FOR SIDE WALL GRAB BAR. PER FBC ACC |
| 604.5.1 SIDE WALL. |
| THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| FROM THE REAR WALL. |
| |
| 2. MIRROR SHOWS 42IN OF FINISHED FLOOR IT SHALL BE 40IN |
| MAX . PER FBC ACC 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES |
| OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE |
| OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM |
| ABOVE THE FINISH FLOOR OR GROUND. |
| |
| 3. SHOW COMPLIANCE WITH FBC ACC 604.2 LOCATION. |
| THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM |
| TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR |
| PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17 |
| INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY |
| ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2. |
| WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR |
| RIGHT-HAND APPROACH. |
| |
| 4. THE TOP OF TOILET SEAT IS SHOWN AS 17IN MAX IT SHALL |
| SHOW 17IN MIN 19IN MAX. PER FBC ACC 604.4 SEATS. |
| THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES |
| (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| |
| 5. THE TOILET PAPER DISPENSER SHALL COMPLY WITH FBC ACC |
| 604.7 DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. |
| |
| 6. THE SERVICE SINK , DRINKING FOUNTAIN AND EYE WASH |
| STATION SHALL CONNECT TO BUILDING DRAIN DOWNSTREAM OF |
| THE BATHROOM GROUP. PER FBC PL 912.1 HORIZONTAL WET |
| VENT PERMITTED. |
| ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE |
| VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE |
| CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND |
| FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION |
| OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM |
| FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH |
| DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT |
| INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE |
| FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO |
| THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL |
| FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| WET VENT. |
| |