2016-07-27 15:18:55BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040632
 ADD: 3001 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY 27/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST FOR WHAT AREA OF WORK IS TO BE COVERED
 UNDER THIS PERMIT. THE PLANS DO INDICATE A 3 HOUR FIRE
 WALL ON THE PLANS IN ONE AREA AND ONLY A 2 HOUR FIRE
 WALL IN ANOTHER AREA. THE SHEET ALS1.1 DO NOT INDICATE
 WHAT OCCUPANCIES ARE BEING SEPARATED BY THESE FIRE
 WALLS. PLEASE NOTE THAT IN THE 2014 FBC ?B TABLE 706.4
 DOES HAVE THE FOOT NOTE (A) THAT ALLOWS FOR THE
 REDUCTION OF 2 HOURS FOR THE OCCUPANCIES COVERED UNDER
 THE FOOTNOTE (A) BUT IF THE AREA ON THE OTHER SIDE OF
 THE FIREWALL IS A S1 OCCUPANCY MOTOR VEHICLE REPAIR
 GARAGE, THEN THERE IS NO REDUCTION IN THE RATING OF THE
 FIRE WALL, PLEASE REVIEW THE 2012 IBC-B TABLE 704.5 AND
 CODE COMMENTARY. PLEASE PROVIDE A NARRATIVE AS TO THE
 AREAS TO BE INCLUDED UNDER THE TYPE VB SPRINKLERED
 CONSTRUCTION.
  
 PLEASE ALSO NOTE IN THE AREA INCREASES TABULATION THE
 PLANS INDICATE THIS IS A 2 STORY BUILDING AND TAKING
 300 % ON AREA INCREASES. THE 300% AREA INCREASES CAN
 ONLY BE TAKEN ON SINGLE STORY BUILDINGS, FOR
 MULTI-STORY BUILDINGS ONLY 200 % INCREASE CAN BE TAKEN
 FOR AUTOMATIC FIRE SPRINKLERS. PLEASE REVIEW THE 2012
 IBC-B CODE COMMENTARY FOR SECTION 506.3. PLEASE ALSO
 REVIEW THE EQUATION 5-1 AND( AT) IN THE FIRST HALF OF
 THE EQUATION.
  
 1ST ROUND OF COMMENTS. THE PERMIT APPLICATION ADDRESS
 AND PCN NUMBER INDICATES THE WORK IS TO BE COMPLETED AT
 THE ADDRESS OF 3001 OKEECHOBEE BLVD. PLEASE DEFINE
 WHERE THE NEW ADDITION ROOF LINE ON THE EAST SIDE WILL
 END AND THE EXISTING ROOF LINE THE WEST SIDE OF THE OF
 THE EXISTING BUILDING TO THE EAST WILL END SHEET A5.0.1
 DETAIL 2.. IT APPEARS THEY WILL BE ADJOINING AND
 CREATING ONE LARGE BUILDING PLEASE PROVIDE COMPLIANCE
 FOR NEW CONSTRUCTION, 2014 FBC-B TABLE 503, 503.1.2.
 BUILDINGS ON THE SAME LOT AND 705.3 BUILDINGS ON THE
 SAME LOT. COMPLIANCE WITH 508.3 NON-SEPARATED USE
 CANNOT BE CONFIRMED UNTIL THE DISTANCE BETWEEN THE 2
 BUILDINGS CAN BE VERIFIED. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 2) 2ND REQUEST. THE SOILS REPORT SUBMITTED IS NOT CLEAR
 AS TO THE LOCATION WHERE THE TEST WAS COMPLETED.
 THE REPORT PREPARED BY ARDAMAN & ASSOCIATES AAI FILE
 NO. 16-1634 INDICATES IT IS FOR THE SCHUMACHER
 AUTOGROUP DELRAY LLC THE ADDRESS OF 3031 OKEECHOBEE
 BLVD WEST PALM BEACH. UNDER THE HEADING SITE LOCATION
 IS INDICATED AS DELRAY BEACH FL. THE SITE VICINITY MAP
 FIGURE NO. 1 IS DELRAY BEACH, FL. THE TEST LOCATION
 PLAN FIGURE NO. 2 ALSO IS FOR THE DELRAY SCHUMACHER ?
 RENOVATION PROJECT, DELRAY BEACH, FLORIDA. IT APPEARS
 THIS REPORT IS FOR THE DELRAY BEACH JOBSITE LOCATION.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. / 2014
 FBC-B 1803.5.2 QUESTIONABLE SOIL.
  
  
  
 1ST ROUND OF COMMENTS. SHEET S4.1 UNDER THE HEADING OF
 FOUNDATION NOTE 1A) THERE WAS A SOILS ENGINEERING
 COMPLETED BY ARDAMAN & ASSOCIATES. NO SOILS REPORTS
 WERE SUBMITTED, 2 ORIGINAL SIGNED AND SEALED REPORTS
 NEED TO BE SUBMITTED FOR COMPLIANCE WITH:
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) COMPLIED.
  
 4) PLEASE PROVIDE COMPLIANCE WITH 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION:
  
 BUILDING PROVISO: 106.1 LIVE LOADS POSTED. WHERE THE
 LIVE LOADS FOR WHICH EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH DESIGN
 LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE OWNER
 IN THAT PART OF EACH STORY IN WHICH THEY APPLY, USING
 DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR DEFACE
 SUCH NOTICES.
  
 BUILDING PROVISO: 106.2 ISSUANCE OF CERTIFICATE OF
 OCCUPANCY. A CERTIFICATE OF OCCUPANCY REQUIRED BY
 SECTION 111 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD
 SIGNS, REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 BUILDING PROVISO: 106.3 RESTRICTIONS ON LOADING. IT
 SHALL BE UNLAWFUL TO PLACE, OR CAUSE OR PERMIT TO BE
 PLACED, ON ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE
 OR PORTION THEREOF, A LOAD GREATER THAN IS PERMITTED BY
 THIS CODE.
  
 5) BUILDING PROVISO: SHEET S-2 THE PRE-ENGINEERED
 MEZZANINE, STAIRS, HANDRAIL & GUARDRAIL SYSTEMS WILL
 NEED THE DESIGN CRITERIA AS LISTED ABOVE IN COMMENT # 3
 AND WILL ALSO NEED TO BE REVIEWED BY THE ENGINEER OF
 RECORD FOR CONFORMANCE WITH THEIR OVERALL DESIGN
 STRUCTURALLY FOR THIS BUILDING AND FOR LOADING. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 6) BUILDING PROVISO: ROOF TOP FIXED LADDER
  
 7)SEMI-COMPLIED. SHEET A1.1.2 SHOWS A LIFT TO THE UPPER
 PARTS RACK STORAGE AREA. THE SQUARE FOOTAGE OF 1499 SQ.
 FT./ 300= OCCUPANT LOAD OF 5, YOU ALWAYS ROUND UP WE DO
 NOT HAVE PARTS OF OCCUPANTS YOU ALWAYS ROUND UP TO THE
 NEXT WHOLE NUMBER. PLEASE NOTE SUBMIT THE MANUFACTURERS
 SPECS ON THE EQUIPMENT FOR THIS ELEVATOR SYSTEM. 3001.2
 REFERENCED STANDARDS.
 EXCEPT AS OTHERWISE PROVIDED FOR IN THIS CODE, THE
 DESIGN, CONSTRUCTION, INSTALLATION, ALTERATION, REPAIR
 AND MAINTENANCE OF ELEVATORS AND CONVEYING SYSTEMS AND
 THEIR COMPONENTS SHALL CONFORM TO ASME A17.1/CSA B44,
 ASME A17.3 AND ASME A18.1, ASME A90.1, ASME B20.1, ALI
 ALCTV, AND ASCE 24 FOR CONSTRUCTION IN FLOOD HAZARD
 AREAS ESTABLISHED IN SECTION 1612.3. THE DIVISION OF
 HOTELS AND RESTAURANTS MAY GRANT EXCEPTIONS, VARIANCES
 AND WAIVERS TO THE ELEVATOR SAFETY CODE AS AUTHORIZED
 BY THE SAFETY CODE FOR ELEVATORS AND ESCALATORS (ASME
 A17.1, SECTION 1.2) AND FLORIDA STATUTES (CHAPTER 120.)
  
  
  
 1ST ROUND OF COMMENTS. PLEASE PROVIDE THE SQUARE
 FOOTAGE FOR THIS AREA AND THE OCCUPANT LOAD TO SEE IF
 THE PLATFORM LIFT HAS TO MEET THE REQUIREMENTS FOR
 VERTICAL ACCESSIBILITY 206.7 .3 FOR NEW BUILDINGS.
 PLEASE ALSO SUPPLY DOCUMENTATION THAT THE PLATFORM LIFT
 SHALL COMPLY WITH ASME A18.1.
  
 8) 2ND REQUEST. RESPONSE INDICATES WILL COMPLY. PLEASE
 PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.4.1..COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF TOP HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 NOTE VASD PRESSURES FOUND ON S-4.2 ARE GOOD. IF EITHER
 THE CONTRACTOR OR THE DESIGNER OF RECORD PREFER TO HAVE
 THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS PLEASE
 DO SO WITHIN THE WRITTEN NARRATIVE RESPONSE.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 9) 2ND REQUEST. RESPONSE INDICATES WILL COMPLY.
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 10) SEMI-COMPLIED. SHEET S-4.1 PROVIDES A GENERIC ROOF
 OPENING FRAMING DETAIL. PLANS INDICATE SEE MECHANICAL
 PLANS FOR OPENING SIZE. PLEASE SEE DETAIL NOTE (14) #
 12 SMS PER BRACKET EQUALLY SPACED. WHAT THE PLANS DO
 NOT INDICATE HOW MANY BRACKETS WILL BE REQUIRED.
 SHEET M2.2 NOTE # 3 INDICATES THE ROOF TOP UNIT
 GREENHECK SPUN ALUMINUM OUTSIDE AIR INTAKE GRSI-8 INCH,
 PLEASE PROVIDE THE ACTUAL OPENING THROUGH THE ROOF FOR
 THE ROOF FRAMING SIZE.
 1ST ROUND COMMENTS. THE STRUCTURAL SHEETS DO NOT
 PROVIDE ROOF FRAMING DETAILS FOR THE ROOF TOP CURBS
 REQUIRED FOR THE ROOFTOP EXHAUST FANS, NOR DOES THE
 MECHANICAL PLANS. FOR ALL ROOF TOP EQUIPMENT, CURBS OR
 A/C STANDS, DETAILED ATTACHMENT TO THE ROOF FRAMING &
 DECK AS WELL AS FROM THE CURB OR ROOF STAND TO THE
 EQUIPMENT ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD
 EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS
 SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS
 THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY,
 GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM
 MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED
 TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?
  
 11A) SHEET M2.1 KEY NOTE 1 INDICATES THE 2 A/C
 CONDENSING UNITS ARE TO BE INSTALLED ON THE ROOF.
 SUBMITTED IS A NOA 15-0902.05 REVIEWED BY DUANE MILLAR
 FOR KAMM CONSULTING. INDICATES (A) REVIEWED NO
 EXCEPTION TAKEN!!!!!! THE STRUCTURAL ENGINEEER OF
 RECORD HAS NOT REVIEWED!!!!
 PLEASE NOTE:
 ** TECHNICAL SHEET 1 THE TYPE OF UNIT IS NOT IDENTIFIED
 STANDARD UNIT, HD HEAVY DUTY ASSEMBLY, OR IS THIS A
 CUSTOM ASSEMBLY.
 ** SHEETS 3-8 HAVE NOT IDENTIFIED SEE STAND EXAMPLE
 MECHANICAL UNIT/ STAND CRITERIA/ FACE AREA, NOTE
 IDENTIFIED.
 ** SHEET 9, 11,12 & 13 SHOW TIE DOWN FRAME ASSEMBLY &
 UNIT TIE DOWN. 11, 12 & 13 ARE SPECIFIC TO RHEEM MODEL
 NUMBERS!!! NOT IDENTIFIED.
 **SHEET 10 IS THE ANCHORING OF THE A/C STAND TO ROOF
 FRAMING ASSEMBLY, NOT IDENTIFIED.
  
  
 11B) COMPLIED. 1013.6 MECHANICAL EQUIPMENT.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  