2016-04-15 14:03:31 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #16040632 |
| 4/15/16 |
| |
| 1) SUBMIT AC COOLING AN HEATING CALCULATIONS FOR AC- 1 |
| & AC-2: SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. |
| 2) SUBMIT ENERGY CALCULATIONS- SECTION C101.4.3 FBC-14 |
| ENERGY CONSERVATION. |
| 3) SHEETS M2.1 & M6.1: THE PARTS RECEIVING AND PARTS |
| DELIVERY AREAS APPEAR TO BE USING AN EXHAUST |
| VENTILATION SYSTEM TO MEET THE O/A REQUIEMENT LISTED IN |
| THE O/A SCHEDULE. PROVIDE THE SIZES OF THE O/A INLET |
| OPENINGS FOR EACH AREA, AND THE SEQUENCE OF OPERATION |
| FOR THE EXHAUST FANS. PLEASE NOTE IF LOUVERS ARE USED |
| TO PROTECT THE EXHAUST AND O/A OPENINGS THEY MUST BE |
| WEATHER RESISTANT PER SECTION 401.5, AND ALSO WIND AND |
| IMPACT RESISTANT PER SECTION 1609.1.2 FBC-14 BUILDING. |
| 4) PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS ON THE |
| PLAN FOR THE AIR INTAKES AND THE EXHAUST OUTLETS- SEE |
| SECTIONS 401.4 AND 501.3.1 FBC-14 MECHANICAL. |
| 5) M2.1 & M6.1: PROVIDE A SEQUENCE OF OPERATION FOR THE |
| EF-2'S IN THE REPAIR GARAGE. |
| 6) PROVIDE WIND LOAD DESIGN CRITERIA AND ENGINEERED |
| DETAILS FOR INSTALLATION OF THE ROOFTOP CONDENSERS AND |
| ROOF RACK, AND THE FANS AND FAN CURBS- SECTION 301.15. |
| 7) SUBMIT MIAMI-DADE NOA'S OR FLORIDA PRODUCT APPROVALS |
| FOR THE ROOF RACK, FANS AND CURBS, AND LOUVERS. ALL |
| SUBMITTALS SHALL BEAR A SHOP DRAWING APPROVAL SIGNATURE |
| BY THE ENGINEER OF RECORD. |
| 8) SHEET A8.0.2:=, DETAIL 4: PLEASE INDICATE THE HEIGHT |
| OF THE PARAPET WALL ABOVE THE FINISHED ROOF LEVEL IN |
| THE DETAIL- PLEASE NOTE A GUARD RAIL MAY BE REQUIRED |
| PER SECTION 304.11 FBC-14 MECHANICAL. |
| 9) INDICATE HOW THE MEZZANINE AREA IS BEING VENTILATED. |
| |