2016-04-18 16:52:29 | JOB PERMIT NUMBER: 16040632 |
| JOB ADDRESS: 3001 OKEECHOBEE BLVD |
| WEST PALM BEACH FLORIDA |
| DATE: APRIL 18 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| - NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO |
| THE FRAMING MEMBER BY MECHANICAL MEANS. SUSPENDED |
| CEILING SHALL ADEQUATE STRENGTH TO ATTACH LIGHTING OR |
| THE LUMINAIRES SHALL BE INDEPENDENTLY SECURED. |
| - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY |
| WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED |
| STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE |
| RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE |
| SEALING MATERIALS. |
| - NEC 210.8 B8 SERVICE BAYS WHERE ELECTRICAL DIAGNOSTIC |
| EQUIPMENT, ELECTRICAL HAND TOOLS, OR PORTABLE LIGHTING |
| EQUIPMENT ARE TO BE USED GFCI PROTECTION IS REQUIRED. |
| - NEC 300.3 C ON WORK BENCH LAYOUT DETAIL MAKE A NOTE |
| THAT DIFFERENT RACEWAYS WILL BE USED FOR LOW VOLTAGE |
| AND POWER CONDUCTORS UNLESS RATED WITH THE SAME |
| INSULATION. |
| - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20 |
| AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET |
| LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF |
| WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL |
| 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING |
| RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE |
| ?WR?. |
| - THE LIGHT ABOVE THE PANELBOARD A SHALL NOT BE |
| CONTROLLED BY AUTOMATIC MEANS ONLY A MANUAL SWITCH |
| SHALL SUFFICE. NEC 110.26 D |
| - NEC 110.26A & 110.24 ARC-FLASH HAZARD WARNING LABEL |
| AND AVAILABLE FAULT CURRENT MARKING IS MISSING FROM |
| ELECTRICAL GENERAL NOTES. |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED DEFICIENCIES. |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS FOR COMPARISON. |
| CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| FBC 2014 5TH ED. NEC 2011 |