2016-04-18 16:52:29JOB PERMIT NUMBER: 16040632
 JOB ADDRESS: 3001 OKEECHOBEE BLVD
 WEST PALM BEACH FLORIDA
 DATE: APRIL 18 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 - NEC 410.36 B LUMINAIRES SHALL BE SECURELY FASTENED TO
 THE FRAMING MEMBER BY MECHANICAL MEANS. SUSPENDED
 CEILING SHALL ADEQUATE STRENGTH TO ATTACH LIGHTING OR
 THE LUMINAIRES SHALL BE INDEPENDENTLY SECURED.
 - ALL ELECTRICAL BOXES IN DEMISING WALL SHALL COMPLY
 WITH NEC 300.21 & FBC-B SECTION 714. ANY FIRE RATED
 STRUCTURE OR SURFACE THAT IS COMPROMISED SHALL BE
 RETURNED TO ITS ORIGINAL FIRE-RATING WITH APPROVED FIRE
 SEALING MATERIALS.
 - NEC 210.8 B8 SERVICE BAYS WHERE ELECTRICAL DIAGNOSTIC
 EQUIPMENT, ELECTRICAL HAND TOOLS, OR PORTABLE LIGHTING
 EQUIPMENT ARE TO BE USED GFCI PROTECTION IS REQUIRED.
 - NEC 300.3 C ON WORK BENCH LAYOUT DETAIL MAKE A NOTE
 THAT DIFFERENT RACEWAYS WILL BE USED FOR LOW VOLTAGE
 AND POWER CONDUCTORS UNLESS RATED WITH THE SAME
 INSULATION.
 - NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?.
 - THE LIGHT ABOVE THE PANELBOARD A SHALL NOT BE
 CONTROLLED BY AUTOMATIC MEANS ONLY A MANUAL SWITCH
 SHALL SUFFICE. NEC 110.26 D
 - NEC 110.26A & 110.24 ARC-FLASH HAZARD WARNING LABEL
 AND AVAILABLE FAULT CURRENT MARKING IS MISSING FROM
 ELECTRICAL GENERAL NOTES.
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  