Notes
Date Text
2016-05-11 12:34:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040632
 ADD: 3001 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 11/ 2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION ADDRESS AND PCN NUMBER
 INDICATES THE WORK IS TO BE COMPLETED AT THE ADDRESS OF
 3001 OKEECHOBEE BLVD. PLEASE DEFINE WHERE THE NEW
 ADDITION ROOF LINE ON THE EAST SIDE WILL END AND THE
 EXISTING ROOF LINE THE WEST SIDE OF THE OF THE EXISTING
 BUILDING TO THE EAST WILL END SHEET A5.0.1 DETAIL 2..
 IT APPEARS THEY WILL BE ADJOINING AND CREATING ONE
 LARGE BUILDING PLEASE PROVIDE COMPLIANCE FOR NEW
 CONSTRUCTION, 2014 FBC-B TABLE 503, 503.1.2. BUILDINGS
 ON THE SAME LOT AND 705.3 BUILDINGS ON THE SAME LOT.
 COMPLIANCE WITH 508.3 NON-SEPARATED USE CANNOT BE
 CONFIRMED UNTIL THE DISTANCE BETWEEN THE 2 BUILDINGS
 CAN BE VERIFIED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED TO DETERMINE CODE COMPLIANCE.
  
 2) SHEET S4.1 UNDER THE HEADING OF FOUNDATION NOTE 1A)
 THERE WAS A SOILS ENGINEERING COMPLETED BY ARDAMAN &
 ASSOCIATES. NO SOILS REPORTS WERE SUBMITTED, 2 ORIGINAL
 SIGNED AND SEALED REPORTS NEED TO BE SUBMITTED FOR
 COMPLIANCE WITH:
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 3) ALS.1.1 NOR S-4.1 PROVIDE COMPLIANCE FOR STAIR &
 FLOOR LOADING.
 2014 FBC-B TABLE 1607.1
 (30) STAIRS 100 PSF
 (31) STORAGE LIGHT 123 PSF/ HEAVY 250 PSF (M).LIVE LOAD
 REDUCTION IS NOT PERMITTED UNLESS SPECIFIC
 EXCEPTIONS OF SECTION 1607.10 APPLY.
  
 4) PLEASE PROVIDE COMPLIANCE WITH 2014 FLORIDA BUILDING
 CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION:
  
 106.1 LIVE LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH
 EACH FLOOR OR PORTION THEREOF OF A
 COMMERCIAL OR INDUSTRIAL BUILDING IS OR HAS BEEN
 DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH THEY
 APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO
 REMOVE OR DEFACE SUCH NOTICES.
  
 106.2 ISSUANCE OF CERTIFICATE OF OCCUPANCY. A
 CERTIFICATE OF OCCUPANCY REQUIRED BY SECTION 111
 SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD SIGNS,
 REQUIRED BY SECTION 106.1, HAVE BEEN INSTALLED.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON
 ANY FLOOR OR ROOF OF A BUILDING, STRUCTURE OR PORTION
 THEREOF, A LOAD GREATER THAN IS PERMITTED BY THIS
  
 5) SHEET S-2 THE PRE-ENGINEERED MEZZANINE, STAIRS,
 HANDRAIL & GUARDRAIL SYSTEMS WILL NEED THE DESIGN
 CRITERIA AS LISTED ABOVE IN COMMENT # 3 AND WILL ALSO
 NEED TO BE REVIEWED BY THE ENGINEER OF RECORD FOR
 CONFORMANCE WITH THEIR OVERALL DESIGN STRUCTURALLY FOR
 THIS BUILDING AND FOR LOADING. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 6) SHEET A8.02 DETAILS 4 & 5 SHOW THE FIXED ROOF TOP
 LADDER. PLEASE SHOW COMPLIANCE WITH :
 2014 FBC-B ? 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS
 OR ELEVATED STRUCTURES.
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
  
 7) SHEET A1.1.1 SHOWS A LIFT TO THE UPPER PARTS RACK
 STORAGE AREA. PLEASE PROVIDE THE SQUARE FOOTAGE FOR
 THIS AREA AND THE OCCUPANT LOAD TO SEE IF THE PLATFORM
 LIFT HAS TO MEET THE REQUIREMENTS FOR VERTICAL
 ACCESSIBILITY 206.7 .3 FOR NEW BUILDINGS. PLEASE ALSO
 SUPPLY DOCUMENTATION THAT THE PLATFORM LIFT SHALL
 COMPLY WITH ASME A18.1.
  
 8) PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1..COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF TOP HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 NOTE VASD PRESSURES FOUND ON S-4.2 ARE GOOD. IF EITHER
 THE CONTRACTOR OR THE DESIGNER OF RECORD PREFER TO HAVE
 THE PRODUCT APPROVALS TO BE DEFERRED SUBMITTALS PLEASE
 DO SO WITHIN THE WRITTEN NARRATIVE RESPONSE.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL.
  
 9) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 10) THE STRUCTURAL SHEETS DO NOT PROVIDE ROOF FRAMING
 DETAILS FOR THE ROOF TOP CURBS REQUIRED FOR THE ROOFTOP
 EXHAUST FANS, NOR DOES THE MECHANICAL PLANS. FOR ALL
 ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, DETAILED
 ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL AS FROM
 THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. 2014
 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 11A) SHEET M2.1 KEY NOTE 1 INDICATES THE 2 A/C
 CONDENSING UNITS ARE TO BE INSTALLED ON THE ROOF BUT NO
 LOCATION IS PROVIDED. SHEET A-2.01 SHOWS THE ROOF HATCH
 WITHIN 10 FEET OF THE ROOF LINE. PLEASE SHOW COMPLIANCE
 WITH: 1013.7 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 11B) 1013.6 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  