Plan Review Notes
Plan Review Notes For Permit 16040583
Permit Number 16040583
Review Stop M
Sequence Number 4
Notes
Date Text
2016-07-08 14:00:574TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040585
 7/8/16
  
 IN AN EFFORT TO HELP EXPEDITE THE APPROVAL OF THE
 MECHANICAL PLANS, PLEASE REVIEW THE COMMENTS BELOW AND
 CONTACT ME AT YOUR EARLIEST CONVENIENCE.
  
 1) REFER TO SECTION 105.3.1.2 WPB AMENDMENTS TO THE
 FBC: THE SUBMITTED AC CALCULATIONS MUST EITHER BEAR THE
 SIGNATURE AND SEAL OF THE MECHANICAL ENGINEER OF
 RECORD, OR BEAR THE SIGNATURE OF THE INSTALLING AC
 CONTRACTOR.
  
 2) DUCT SMOKE DETECTORS WHERE REQUIRED BY SECTION
 606.2.1 SHALL BE INSTALLED IN THE RETURN AIR SYSTEMS.
  
 3) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 INSTALLATION OF THE ROOFTOP CONDENSERS, THE CONDENSER
 STANDS, AND EXHAUST FANS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  