Plan Review Notes
Plan Review Notes For Permit 16040583
Permit Number 16040583
Review Stop M
Sequence Number 3
Notes
Date Text
2016-06-27 16:01:023RD REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CODES
 PERMIT 16040583
 6/27/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 PROPOSED AC SYSTEMS- SECTION C403.2.1 CALCULATION OF
 HEATING AND COOLING LOADS FBC-14 ENERGY CONSERVATION.
  
 2) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH
 SECTION C101.4.3.
  
 3) M-1: PROVIDE THE CORRECT RETURN AIR SYMBOL FOR AHU-1
 AT THE HVAC ROOM, AND AT THE OFFICE 101 RISER.
  
 4) M-1: NO RETURN AIR DUCT IS SHOWN FOR AHU-3 AT THE
 HVAC ROOM.
  
 5) M-1: THE OAI-1 APPEARS TO BE MISLABELED AS EAO-2
  
 6) CLARIFY IF THERE IS A DOOR FOR THE HVAC ROOM AND
 INDICATE THE TYPE AND SIZE.
  
 7) PROVIDE A ROOF PLAN SHOWING THE LOCATIONS OF ALL
 ROOF TOP EQUIPMENT AND CLEARANCE DISTANCES FOR AIR
 INTAKES TO EXHAUST AND VENT OUTLETS- SEE SECTION 401.4
 FBC-14 MECHANICAL
  
 8) PROVIDE SHUTOFF DAMPER CONTROLS FOR THE O/A INAKES
 AND RELIEF EXHAUSTS THAT WILL AUTOMATICALY SHUT WHEN
 THE SYSTEMS OR SPACES ARE NOT IN USE- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  