2016-06-02 12:21:322ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16040583
 6/2/16
  
 1) SUBMIT AC CHANGEOUT FORMS AND AHRI CERTIFICATES FOR
 THE SYSTEMS BEING REPLACED AS INDICATED ON SHEET M-2.
  
 2) THE SCOPE OF WORK FOR MECHANICAL IS NOT CLEAR: THE
 1ST FLOOR AND MEZZANINE DUCT LAYOUT PLANS ON M-1 ARE
 LABELED AS "EXISTING", HOWEVER THE HVAC NOTES ON M-2
 APPEAR TO INDICATE ALL NEW DUCT WORK, EXHAUST FANS, AND
 OTHER COMPONENTS. PLEASE CLARIFY AND USE LETTERED
 SYMBOLS SUCH AS "E" FOR EXISTING, "N" FOR NEW, "R" FOR
 RELOCATED AT DIFFUSER AND GRILL LOCATIONS, USE DOTTED
 LINES TO INDICATE REMOVED OR RELOCATED DUCTS AND SOLID
 LINES TO INDICATE NEW, REPLACED, OR RELOCATED DUCTS. IN
 REGARD TO THE EXISTING PLANS PLEASE REVIEW THESE
 COMMENTS:
  
 A) LABEL THE 8X6 DUCT IN THE OFFICE 108 AND THE CFMS.
 B) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE
 OPEN AREA SHOWN ON THE 1ST FLOOR, CLARIFY WHY EXHAUST
 IS NEEDED (WHAT PROCESSES OR WORK IS BEING CONDUCTED IN
 THE ROOM?), AND LABEL THE EXHAUST DUCT TERMINATION
 LOCATION.
 C) PROVIDE WIND LOAD DEIGN CRITERIA AND ENGINEERED
 DETAILS FOR INSTALLATION OF THE NEW ROOF TOP CONDENSER
 AND CONDENSER STANDS, AND EXHAUST TERMINATION CAPS-
 SECTION 301.15.
 D) THE TOILET ROOM EXHAUST FANS SHALL HAVE CAPACITIES
 OF 70 CFMS EACH PER TABLE 403.3 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  