Plan Review Notes For Permit 16040577 |
Permit Number |
16040577 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-12 18:27:58 | ELECTRICAL REVIEW COMMENTS | | REVIEWED FOR COMPLIANCE WITH: | | 5TH EDITION OF THE FBC 2014 & NFPA 70 (NEC) 2011 | | EDITION | | | | CORRECTIONS REQUIRED: | | 1. THE PROVIDED SITE PLAN REFLECTS NUMEROUS | | INSTALLATION PLEASE INDICATE WHICH OF THOSE IS THE | | PROPOSED. | | 2. ALONG WITH THE SUBMITTED LOAD CALCS, YOU WILL NEED | | TO PROVIDE A SERVICE RISER DIAGRAM TO INCLUDE THE | | REQUIRED PROTECTION FROM PHYSICAL DAMAGE. | | 3. SHOW HOW WILL THE ELECTRICAL APPARATUS BE SECURED TO | | THE CONCRETE POLE. | | 4. THE SERVICE EQUIPMENT SHALL BE LABELED TO WARN | | AGAINST ARC-FLASH HAZARDS AS INDICATED BY NEC 110.16 | | AND BE DURABLY MARKED TO INDICATE THE MAXIMUM AVAILABLE | | FAULT CURRENT AS INSTRUCTED IN NEC 110.24. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|