Plan Review Notes
Plan Review Notes For Permit 16040574
Permit Number 16040574
Review Stop B
Sequence Number 3
Notes
Date Text
2016-10-21 13:33:28BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040574
 ADD: 1025 7TH ST.
 CONT: T. B. D. / TO BE DETERMINED
 TEL: 561-310-7829
 E-MAIL: ?????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. OCT. 21/ 2016
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) 2ND REQUEST. THE PROPOSED VALUE OF THE PROJECT IS
 EXTREMELY LOW AT $75,000.00 IN VALUE. USING THE ICC
 BUILDING VALUATION CHARTS FROM AUGUST 2015 FOR THE
 SQUARE FOOTAGE OF :
 A3/ III-B 937 SQ. FT. X $137.12 = $ 128,481.44
 B / III-B 1,631 SQ. FT. X $152.55 = $ 248,809.05
 $ 377,290.00 TOTAL VALUE FOR THE BUILDING
 ONLY!!!!!!!!!!
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4-6) COMPLIED
  
 7A) 3RD REQUEST. SHEET A3 DETAIL 14 ALSO INDICATES THE
 USE OF STUCCO AND THE USE OF WIRE LATH. PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-B 2510.6 WATER-RESISTIVE
 BARRIERS. WATER-RESISTIVE BARRIERS SHALL BE INSTALLED
 AS REQUIRED IN SECTION 1404.2 AND, WHERE APPLIED OVER
 WOOD-BASED SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 1405.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 7B) NEW COMMENT, SHEET A2.1 ON THE NORTH AND SOUTH
 GABLE WALLS THE PLANS HAVE A DISCREPANCY, THE PLANS
 APPEAR TO HAVE STUCCO GABLE ENDS, BUT THERE IS NOW A
 NOTE TO APPLY ASPHALT SINGLES THERE ALSO, DISCREPANCY
 IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 8-13) COMPLIED. 2FT OVERHANG FOR THE ROOF TRUSSES.
  
  
 14A) 3RD REQUEST . IF THE DESIGNER OF RECORD WISHES TO
 DEFER THE PRODUCT APPROVALS UNTIL AFTER PERMIT ISSUANCE
 A WRITTEN RESPONSE NEEDS TO OCCUR. 107.3.4.2 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PRODUCT APPROVALS PRODUCT APPROVALS MAYBE A DEFERRED
 SUBMITTAL: 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 14B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 15-16) COMPLIED.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  