2016-07-20 06:33:432ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS:
  
 9. PROVIDE EXISTING ONE-LINE DIAGRAM AND ALL NEW
 SERVICE EQUIPMENT WITH ASSOCIATED WIRE SIZES, CONDUIT
 SIZE AND GROUNDING SCHEME. FBC 107.3.5.- PLEASE NOTE
 THAT THE NEW SERVICE SHOWN WILL REQUIRE A AIC
 CALCULATION NEC 110.9. RISER DIAGRAM SHOWN NOT IN
 COMPLIANCE WITH NEC 2011. SERVICE CONDUCTORS AND FEEDER
 CONDUCTORS SHOWN FOR 241AMP CALCULATED LOAD AND MAIN
 BREAKER 300A IS UNDERSIZED PER NEC 310.15 B 16 TABLE OF
 AMPACITIES AND NEC 240.4 OVERCURRENT SELECTION. SHOW
 CONDUCTORS AT THE SERVICE DISC TO BE FUSED AND LABEL
 SERVICE DISCONNECT TO BE RATED FOR SERVICE ENTRANCE
 EQUIPMENT. AN EQUIPMENT GROUNDING CONDUCTOR TO BE
 INSTALLED TO PANEL A PER NEC 250.122. CLARIFY #1
 CONDUCTORS SHOWN FROM METER TO PANEL A, NEED TO
 COORELATE.
  
 1- SHOW ON FLOOR PLAN WHERE THE SERVICE IS LOCATED.
 COULD NOT LOCATE PANELBOARD IN HALLWAY AS INDICATED ON
 NARRATIVE. PROVIDE NOTES TO INDICATE PROPER SINAGE
 REQUIRED AT THE SERVICE, SEE NEC 110.16 ARC FLASH
 HAZARD WARNINGS AND NEC 110.24 FIELD MARKING OF
 AVAILABLE FAULT CURRENT. SEE VERBIAGE IN CODE SECTION.
 NOTES WILL SUFFICE.
  
 2- FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. PLEASE
 FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  