2016-07-20 15:29:59BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040574
 ADD: 1025 7TH ST.
 CONT: T. B. D. / TO BE DETERMINED
 TEL: 561-310-7829
 E-MAIL: ?????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JULY 20/ 2016
 ACTION: DENIED
  
 1-2) COMPLIED
  
 3) 2ND REQUEST. THE PROPOSED VALUE OF THE PROJECT IS
 EXTREMELY LOW AT $75,000.00 IN VALUE. USING THE ICC
 BUILDING VALUATION CHARTS FROM AUGUST 2015 FOR THE
 SQUARE FOOTAGE OF :
 A3/ III-B 937 SQ. FT. X $137.12 = $ 128,481.44
 B / III-B 1,631 SQ. FT. X $152.55 = $ 248,809.05
 $ 377,290.00 TOTAL VALUE FOR THE BUILDING
 ONLY!!!!!!!!!!
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4A)SEMI-COMPLIED THE DOOR SCHEDULE STILL DOES NOT
 PROVIDE IN HOURS OR MINUTES THE FIRE RATING OF THE
 DOORS (OPENING PROTECTIVES).
 COMMENT 1ST REVIEW. SHEET A4/ LIFE SAFETY SHEET DOES
 NOT SHOW THE CORRIDOR AS A FIRE RATED CORRIDOR. PLEASE
 REVIEW TABLE 1018.1 OF THE 2014 FBC-B. FOR BOTH
 ASSEMBLY AND BUSINESS OCCUPANCIES OF NON-FIRE
 SPRINKLERED BUILDINGS WITH AN OCCUPANT LOAD GREATER
 THAN 30 A ONE HOUR FIRE RATED CORRIDOR IS REQUIRED WITH
 REQUIRED OPENING PROTECTIVES FOR DOORS IN COMPLIANCE OF
 TABLE 716.5. 20 MINUTE FIRE RATED DOORS, SEE FOOTNOTE
 B.
  
 4B) SEMI ?COMPLIED. THE PLANS NOW SHOW A FIRE RATED
 CORRIDOR WITH THE FIRE RATED WALLS EXTENDING ALL THE
 WAY TO THE ROOF LINE. THE PLANS NOW SHOW FIRE DAMPERS
 WITHIN THE WALLS. THE PLANS DO NOT INDICATE IS HOW
 ACCESS TO THE FIRE DAMPERS WILL BE MAINTAINED NOR THE
 LOCATION OF THE ACCESS PANELS.
 717.4 ACCESS AND IDENTIFICATION. FIRE AND SMOKE DAMPERS
 SHALL BE PROVIDED WITH AN APPROVED MEANS OF ACCESS,
 WHICH IS LARGE ENOUGH TO PERMIT INSPECTION AND
 MAINTENANCE OF THE DAMPER AND ITS OPERATING PARTS. THE
 ACCESS SHALL NOT AFFECT THE INTEGRITY OF
 FIRE-RESISTANCE-RATED ASSEMBLIES. THE ACCESS OPENINGS
 SHALL NOT REDUCE THE FIRE-RESISTANCE RATING OF THE
 ASSEMBLY. ACCESS POINTS SHALL BE PERMANENTLY IDENTIFIED
 ON THE EXTERIOR BY A LABEL HAVING LETTERS NOT LESS THAN
 1/2 INCH (12.7 MM) IN HEIGHT READING: FIRE/SMOKE
 DAMPER, SMOKE DAMPER OR FIRE DAMPER. ACCESS DOORS IN
 DUCTS SHALL BE TIGHT FITTING AND SUITABLE FOR THE
 REQUIRED DUCT CONSTRUCTION
  
 COMMENT FROM THE 1ST REVIEW. PLEASE SHOW HOW THE 1 HOUR
 FIRE RATED CORRIDOR IS TO BE BUILT INCLUDING THE FIRE
 RATING OF WALLS TO THE ROOF SHEATHING ON BOTH SIDES OF
 THE CORRIDOR OR IS THERE GOING TO BE A FIRE RATED
 CEILING ASSEMBLY? THE MECHANICAL SHEET M1 DOES NOT SHOW
 EITHER THE DUCTS PENETRATING THE CORRIDOR CEILING WITH
 FIRE DAMPERS. DEPENDING WHERE THE MAIN TRUNK LINE IS
 PLACED IF ABOVE IN THE ATTIC OR BELOW A RATED CORRIDOR
 CEILING EITHER CEILING DAMPERS WILL BE REQUIRED OR FIRE
 DAMPERS IN THE CORRIDOR WALLS. SEE FBC-B 717.5.4.1
 CORRIDORS. A LISTED SMOKE DAMPER DESIGNED TO RESIST THE
 PASSAGE OF SMOKE SHALL BE PROVIDED AT EACH POINT A DUCT
 OR AIR TRANSFER OPENING PENETRATES A CORRIDOR ENCLOSURE
 REQUIRED TO HAVE SMOKE AND DRAFT CONTROL DOORS IN
 ACCORDANCE WITH SECTION 716.5.3.
  
 5) COMPLIED.
  
 6) 2ND REQUEST. CORRECTED THE DETAIL 14 ON SHEET A3 BUT
 THE FOUNDATION SCHEDULE ON SHEET A5 STILL INDICATES THE
 FOUNDATION HEIGHT OF 16 INCHES. THE COMMENTS BELOW FROM
 THE 1ST ROUND OF COMMENTS STILL APPLY.
 1ST ROUND COMMENT. FOUNDATION SHEET (A5) VERSES SHEET
 A3 DETAIL 14 CUT SECTION OF EXTERIOR WALL AND
 FOUNDATION. SHEET A5 THE PERIMETER FOUNDATION IS
 INDICATED AS 18 IN. WIDE X 16IN. DEEP. PLEASE SEE SHEET
 A3 DETAIL # 14. THE FINISH FLOOR IS SHOWN AT ELEVATION
 0-0 FT. THE BOTTOM SILL PLATE IS RECESSED, THE
 DIMENSION NOT GIVEN. THE STUCCO SIDING AND
 SUB-SHEATHING STOP ABOVE THE BOTTOM HALF OF THE BOTTOM
 SILL PLATE NOT PROVIDING PROTECTION AGAINST THE WEATHER
 AND PROMOTING ROT. THE 2012 ICC-B CODE COMMENTARY
 2304.11.2.6 ON THIS SECTION INDICATES THE STUCCO AND
 SHEATHING SHOULD EXTEND AT LEAST 1 INCH BELOW THE TOP
 OF THE FOUNDATION. THEN THE 6 INCH CLEARANCE BETWEEN
 THE STUCCO AND SUB-SHEATHING TO EXPOSED GRADE SHOULD
 OCCUR. SECTION 1809.4 OF THE 2014 FBC-B REQUIRES THE
 FOUNDATION TO BE A MINIMUM OF 12 INCHES BELOW GRADE TO
 THE BOTTOM OF THE FOUNDATION. THE VERTICAL DIMENSION OF
 THE FOUNDATION NEEDS TO BE INCREASED TO MEET ALL OF
 THESE CODE REQUIREMENTS.
  
 7) 2ND REQUEST. SHEET A3 DETAIL 14 ALSO INDICATES THE
 USE OF STUCCO AND THE USE OF WIRE LATH. PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-B 2510.6 WATER-RESISTIVE
 BARRIERS. WATER-RESISTIVE BARRIERS SHALL BE INSTALLED
 AS REQUIRED IN SECTION 1404.2 AND, WHERE APPLIED OVER
 WOOD-BASED SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 1405.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 8) COMPLIED. 2FT OVERHANG FOR THE ROOF TRUSSES.
  
 9) SEMI-COMPLIED. SHEET A-6 DETAIL 4/ A5 (FOUND ON A6)
 THE NEW DETAIL SHOWS A DROPPED GABLE END TRUSS AND A
 2X4 OUTLOOKER TRUSS CANTILEVERED OVER THE DROPPED GABLE
 END TRUSS. THE ROOF FRAMING PLAN ON THE LEFT SIDE OF
 THE PLAN STILL SHOWS THE LADDER TYPE FRAMING. THE 2X4
 OUTLOOKERS ARE NOT CONTINUED IN TO THE 2ND TRUSS,
 (FIRST COMMON TRUSS). PLEASE ALSO TAKE NOTE OF THE
 HEIGHT OF THE A2 TRUSS 5 FT. 9 1/16 INCH AND THE
 DROPPED GABLE TRUSS OF 5 FT. 3 7/8 INCHES = EQUALS TO A
 5 ? INCH FRAMING MEMBER FOR OUTLOOKERS, NOT A 2X4 AT 3
 ? INCHES. PLEASE CHECK MY MATH FOR ACCURACY.
 1ST ROUND OF COMMENTS. SHEET A-6. THE TRUSS LAYOUT
 SHEET SHOWS WHAT APPEARS TO BE A 2 FT. OVERHANG ON THE
 GABLE END WALLS, THIS DETAIL MAY BE REQUIRED TO BE A
 DROPPED GABLE END. PLEASE NOTE THIS TYPE OF LATTER TYPE
 OVERHANG IS USUALLY FOUND ON TRUSS OVERHANGS OF 12
 INCHES. THE WOOD TRUSSES SHALL BE DESIGNED IN
 ACCORDANCE WITH SECTION 2303.4.
 2303.4.2 TRUSS PLACEMENT DIAGRAM. THE TRUSS
 MANUFACTURER SHALL PROVIDE A TRUSS PLACEMENT DIAGRAM
 THAT IDENTIFIES THE PROPOSED LOCATION FOR EACH
 INDIVIDUALLY DESIGNATED TRUSS AND REFERENCES THE
 CORRESPONDING TRUSS DESIGN DRAWING. THE TRUSS PLACEMENT
 DIAGRAM SHALL BE PROVIDED AS PART OF THE TRUSS
 SUBMITTAL PACKAGE, AND WITH THE SHIPMENT OF TRUSSES
 DELIVERED TO THE JOB SITE. TRUSS PLACEMENT DIAGRAMS
 THAT SERVE ONLY AS A GUIDE FOR INSTALLATION AND DO NOT
 DEVIATE FROM THE PERMIT SUBMITTAL DRAWINGS SHALL NOT BE
 REQUIRED TO BEAR THE SEAL OR SIGNATURE OF THE TRUSS
 DESIGNER.
 2303.4.3 TRUSS SUBMITTAL PACKAGE. THE TRUSS SUBMITTAL
 PACKAGE PROVIDED BY THE TRUSS MANUFACTURER SHALL
 CONSIST OF EACH INDIVIDUAL TRUSS DESIGN DRAWING, THE
 TRUSS PLACEMENT DIAGRAM, THE PERMANENT INDIVIDUAL TRUSS
 MEMBER RESTRAINT/BRACING METHOD AND DETAILS AND ANY
 OTHER STRUCTURAL DETAILS GERMANE TO THE TRUSSES; AND,
 AS APPLICABLE, THE COVER/TRUSS INDEX SHEET.
  
 10-12) COMPLIED.
  
 13) 2ND REQUEST. SHEET A2.1 THE SOUTH ELEVATION SHOWS
 ARCHITECTURAL DETAILS OF COLUMNS AND PEDIMENT PLEASE
 SHOW A CUR THROUGH SECTION OF THIS AREA FOR A BETTER
 UNDERSTANDING OF THE DEPTH OF THESE ELEMENTS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 14A) PRODUCT APPROVALS MAYBE A DEFERRED SUBMITTAL: 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 14B) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 15) COMPLIED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715