Plan Review Notes For Permit 16040574 |
Permit Number |
16040574 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-04-13 16:53:00 | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED. | | | | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | ON WPB PERMIT APPLICATION UNDER "FURTHER WORK | | DESCRIPTION" IT STATES "ADDING A 70' X 40' ADDITION TO | | OUR EXISTING CHURCH" | | (1)PROVIDE HEAT LOAD CALCULATIONS AND ENERGY | | CALCULATIONS FOR TOTAL SQFT. UNDER AIR. | | | | 107.2 | | (2) PROVIDE CFM QUANTITIES ON ALL SUPPLY AND RETURN | | GRILLS. | | (3)PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014 | | WIND LOAD REQUIREMENTS. | | (4)EXPLAIN THE 8" X 8" TRANSFER OUTSIDE OF PANTRY AREA. | | (5)PROVIDE OUTSIDE AIR FOR EACH AHU. | | (6)PROVIDE OUTSIDE AIR DUCTS (TO INCLUDE DUCT SIZES, | | LOCATION, AND CFM TOTALS). | | | | |
|