2016-04-13 16:53:00WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED REPLACED SHEETS DETACHED.
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 ON WPB PERMIT APPLICATION UNDER "FURTHER WORK
 DESCRIPTION" IT STATES "ADDING A 70' X 40' ADDITION TO
 OUR EXISTING CHURCH"
 (1)PROVIDE HEAT LOAD CALCULATIONS AND ENERGY
 CALCULATIONS FOR TOTAL SQFT. UNDER AIR.
  
 107.2
 (2) PROVIDE CFM QUANTITIES ON ALL SUPPLY AND RETURN
 GRILLS.
 (3)PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014
 WIND LOAD REQUIREMENTS.
 (4)EXPLAIN THE 8" X 8" TRANSFER OUTSIDE OF PANTRY AREA.
 (5)PROVIDE OUTSIDE AIR FOR EACH AHU.
 (6)PROVIDE OUTSIDE AIR DUCTS (TO INCLUDE DUCT SIZES,
 LOCATION, AND CFM TOTALS).
  
  