2016-04-13 12:30:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) SHEET A 1 - IT IS NOTED THAT DOORS IN THE CORRIDOR |
| ARE INDICATED AS FIRE RATED; NO FIRE RATING INDICATED, |
| NO RATED HARDWARE. THE CORRIDOR CONSTRUCTION SHALL |
| COMPLY WITH NFPA 101, CHAPTER 12. |
| |
| 12.3.6 CORRIDORS. INTERIOR CORRIDORS AND LOBBIES SHALL |
| BE CONSTRUCTED IN ACCORDANCE WITH 7.1.3.1 AND SECTION |
| 8.3, UNLESS OTHERWISE PERMITTED BY ONE OF THE |
| FOLLOWING: |
| (1) CORRIDOR AND LOBBY PROTECTION SHALL NOT BE REQUIRED |
| WHERE ASSEMBLY ROOMS SERVED BY THE CORRIDOR OR LOBBY |
| HAVE AT LEAST 50 PERCENT OF THEIR EXIT CAPACITY |
| DISCHARGING DIRECTLY TO THE OUTSIDE, INDEPENDENT OF |
| CORRIDORS AND LOBBIES. |
| (2) CORRIDOR AND LOBBY PROTECTION SHALL NOT BE REQUIRED |
| IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, |
| SUPERVISEDAUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| SECTION 9.7. |
| (3) LOBBIES SERVING ONLY ONE ASSEMBLY AREA THAT MEET |
| THE REQUIREMENTS FOR INTERVENING ROOMS (SEE 7.5.1.6) |
| SHALL NOT BE REQUIRED TO HAVE A FIRE RESISTANCE RATING. |
| (4) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A |
| 1-HOUR FIRE RESISTANCE RATING WHERE TESTED AS A WALL, |
| THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT |
| THE CORRIDOR CEILING. |
| (5) CORRIDOR AND LOBBY PROTECTION SHALL NOT BE REQUIRED |
| IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, TOTAL |
| (COMPLETE) COVERAGE SMOKE DETECTION SYSTEM PROVIDING |
| OCCUPANT NOTIFICATION AND INSTALLED IN ACCORDANCE WITH |
| SECTION 9.6. |
| |
| THE DESIGN DOES NOT MEET 1-5 ABOVE.... |
| |
| 7.1.3.1 EXIT ACCESS CORRIDORS. CORRIDORS USED AS EXIT |
| ACCESS AND SERVING AN AREA HAVING AN OCCUPANT LOAD |
| EXCEEDING 30 SHALL BE SEPARATED FROM OTHER PARTS OF THE |
| BUILDING BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE |
| RESISTANCE RATING IN ACCORDANCE WITH SECTION 8.3, |
| UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING: |
| (1) THIS REQUIREMENT SHALL NOT APPLY TO EXISTING |
| BUILDINGS, PROVIDED THAT THE OCCUPANCY CLASSIFICATION |
| DOES NOT CHANGE. |
| (2) THIS REQUIREMENT SHALL NOT APPLY WHERE OTHERWISE |
| PROVIDED IN CHAPTERS 11 THROUGH 43. |
| |
| THE CORRIDOR SHALL HAVE A 1-HOUR FIRE RESISTIVE RATING |
| ON ALL SIDES, INCLUDING DOORS AND HARDWARE, INCLUDING |
| CLOSERS. |
| |
| 2) SHEET A 1 - DOOR 4 IS NOT INDICATED AS FIRE RATED OR |
| WITH EXIT HARDWARE. PLEASE PROVIDE RATING PER THE CODE |
| NARRATIVE ABOVE. |
| |
| 3) SHEET A 1 - AN EXIT SIGN IS NEEDED INSIDE THE |
| FELLOWSHIP HALL AT THE DOUBLE DOORS. |
| |
| 4) SHEET E 1 - NO EXIT SIGNS OR EMERGENCY LIGHTS ARE |
| INDICATED. PLEASE PROVIDE IN COMPLIANCE WITH NFPA 101, |
| CHAPTER 12 & CHAPTER 7 |
| |
| 12.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF |
| EGRESS, OTHER THAN FOR PRIVATE PARTY TENTS NOT |
| EXCEEDING 1200 FT2 (112 M2), SHALL BE ILLUMINATED IN |
| ACCORDANCE WITH SECTION 7.8. |
| 12.2.9 EMERGENCY LIGHTING. |
| 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN |
| ACCORDANCE WITH SECTION 7.9. |
| |
| 12.2.10 MARKING OF MEANS OF EGRESS. |
| 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS |
| IN ACCORDANCE WITH SECTION 7.10. |
| |
| 7.8 ILLUMINATION OF MEANS OF EGRESS. |
| 7.8.1 GENERAL. |
| 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY |
| BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11 |
| THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING |
| TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT |
| DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES, |
| CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT |
| PASSAGEWAYS LEADING TO A PUBLIC WAY. |
| 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE |
| CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF |
| OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE |
| FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2. |
| |
| 7.9 EMERGENCY LIGHTING. |
| 7.9.1 GENERAL. |
| 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9 |
| FOR THE FOLLOWING: |
| (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| 11 THROUGH 43 |
| |
| 7.9.2 PERFORMANCE OF SYSTEM. |
| 7.9.2.1* EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A |
| MINIMUMOF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL |
| LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE |
| ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT |
| LESS THAN AN AVERAGE OF 1 FT-CANDLE (10.8 LUX) AND, AT |
| ANY POINT, NOT LESS THAN 0.1 FT-CANDLE (1.1 LUX), |
| MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL. |
| ILLUMINATION LEVELS SHALL BE PERMITTED TO DECLINE TO |
| NOT LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX) |
| AND, ATANY POINT, NOT LESS THAN 0.06 FT-CANDLE (0.65 |
| LUX) AT THE END OF 1? HOURS. A MAXIMUM-TO-MINIMUM |
| ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE |
| EXCEEDED. |
| |
| PETER LEDUC |
| FIRE MARSHAL |