Plan Review Notes For Permit 16040574
Permit Number 16040574
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-04-13 12:30:39THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1 - IT IS NOTED THAT DOORS IN THE CORRIDOR
 ARE INDICATED AS FIRE RATED; NO FIRE RATING INDICATED,
 NO RATED HARDWARE. THE CORRIDOR CONSTRUCTION SHALL
 COMPLY WITH NFPA 101, CHAPTER 12.
  
 12.3.6 CORRIDORS. INTERIOR CORRIDORS AND LOBBIES SHALL
 BE CONSTRUCTED IN ACCORDANCE WITH 7.1.3.1 AND SECTION
 8.3, UNLESS OTHERWISE PERMITTED BY ONE OF THE
 FOLLOWING:
 (1) CORRIDOR AND LOBBY PROTECTION SHALL NOT BE REQUIRED
 WHERE ASSEMBLY ROOMS SERVED BY THE CORRIDOR OR LOBBY
 HAVE AT LEAST 50 PERCENT OF THEIR EXIT CAPACITY
 DISCHARGING DIRECTLY TO THE OUTSIDE, INDEPENDENT OF
 CORRIDORS AND LOBBIES.
 (2) CORRIDOR AND LOBBY PROTECTION SHALL NOT BE REQUIRED
 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISEDAUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH
 SECTION 9.7.
 (3) LOBBIES SERVING ONLY ONE ASSEMBLY AREA THAT MEET
 THE REQUIREMENTS FOR INTERVENING ROOMS (SEE 7.5.1.6)
 SHALL NOT BE REQUIRED TO HAVE A FIRE RESISTANCE RATING.
 (4) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR FIRE RESISTANCE RATING WHERE TESTED AS A WALL,
 THE CORRIDOR WALLS SHALL BE PERMITTED TO TERMINATE AT
 THE CORRIDOR CEILING.
 (5) CORRIDOR AND LOBBY PROTECTION SHALL NOT BE REQUIRED
 IN BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED, TOTAL
 (COMPLETE) COVERAGE SMOKE DETECTION SYSTEM PROVIDING
 OCCUPANT NOTIFICATION AND INSTALLED IN ACCORDANCE WITH
 SECTION 9.6.
  
 THE DESIGN DOES NOT MEET 1-5 ABOVE....
  
 7.1.3.1 EXIT ACCESS CORRIDORS. CORRIDORS USED AS EXIT
 ACCESS AND SERVING AN AREA HAVING AN OCCUPANT LOAD
 EXCEEDING 30 SHALL BE SEPARATED FROM OTHER PARTS OF THE
 BUILDING BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE RATING IN ACCORDANCE WITH SECTION 8.3,
 UNLESS OTHERWISE PERMITTED BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO EXISTING
 BUILDINGS, PROVIDED THAT THE OCCUPANCY CLASSIFICATION
 DOES NOT CHANGE.
 (2) THIS REQUIREMENT SHALL NOT APPLY WHERE OTHERWISE
 PROVIDED IN CHAPTERS 11 THROUGH 43.
  
 THE CORRIDOR SHALL HAVE A 1-HOUR FIRE RESISTIVE RATING
 ON ALL SIDES, INCLUDING DOORS AND HARDWARE, INCLUDING
 CLOSERS.
  
 2) SHEET A 1 - DOOR 4 IS NOT INDICATED AS FIRE RATED OR
 WITH EXIT HARDWARE. PLEASE PROVIDE RATING PER THE CODE
 NARRATIVE ABOVE.
  
 3) SHEET A 1 - AN EXIT SIGN IS NEEDED INSIDE THE
 FELLOWSHIP HALL AT THE DOUBLE DOORS.
  
 4) SHEET E 1 - NO EXIT SIGNS OR EMERGENCY LIGHTS ARE
 INDICATED. PLEASE PROVIDE IN COMPLIANCE WITH NFPA 101,
 CHAPTER 12 & CHAPTER 7
  
 12.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF
 EGRESS, OTHER THAN FOR PRIVATE PARTY TENTS NOT
 EXCEEDING 1200 FT2 (112 M2), SHALL BE ILLUMINATED IN
 ACCORDANCE WITH SECTION 7.8.
 12.2.9 EMERGENCY LIGHTING.
 12.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 7.9.
  
 12.2.10 MARKING OF MEANS OF EGRESS.
 12.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN ACCORDANCE WITH SECTION 7.10.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN7.8.1.2.2.
  
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9
 FOR THE FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
  
 7.9.2 PERFORMANCE OF SYSTEM.
 7.9.2.1* EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUMOF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE (10.8 LUX) AND, AT
 ANY POINT, NOT LESS THAN 0.1 FT-CANDLE (1.1 LUX),
 MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL.
 ILLUMINATION LEVELS SHALL BE PERMITTED TO DECLINE TO
 NOT LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX)
 AND, ATANY POINT, NOT LESS THAN 0.06 FT-CANDLE (0.65
 LUX) AT THE END OF 1? HOURS. A MAXIMUM-TO-MINIMUM
 ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE
 EXCEEDED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  