Plan Review Notes For Permit 16040574
Permit Number 16040574
Review Stop E
Sequence Number 1
Notes
Date Text
2016-04-18 11:14:26INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE DELETE FROM ELECTRICAL NOTES LIST THE
 NON-APPLICABLE NOTES FOR RESIDENTIAL DWELLINGS.
 2. PROVIDE A NOTE TO PROVIDE TAMPER RESISTANT
 RECEPTACLE TO THE CLASSROOM AREAS AS SHOWN ON DRAWINGS.
 NEC 406.14
 3. CLARIFY GFCI SHOWN IN SHOWER AREA, NEC 406.9C
 4. ADDRESS ALL FIRE DEPARTMENT COMMENTS RELATED TO THE
 ELECTRICAL SCOPE.
 5. SHOW ON DRAWINGS THE CIRCUIT DESIGNATION FOR ALL
 POWER AND LIGHTING OUTLETS. FBC 107.3.5
 6. CLARIFY ON DRAWINGS WHAT IS NEW AND WHAT IS
 EXISTING, BY DESIGNATING N OR E AS SYMBOLS.
 7. SHOW ON PLANS THE LOCATION OF THE ELECTRICAL SERVICE
 AND THE AIR HANDLER EQUIPMENT.
 8. PLEASE CLARIFY THE OCCUPANCY SENSORS SHOWN FOR THE
 FAN MOTOR IN CLASSROOM.
 9. PROVIDE EXISTING ONE-LINE DIAGRAM AND ALL NEW
 SERVICE EQUIPMENT WITH ASSOCIATED WIRE SIZES, CONDUIT
 SIZE AND GROUNDING SCHEME. FBC 107.3.5
 10. SHOW ON PANEL SCHEDULE THE CIRCUIT IDENTIFICATION
 FOR THE AREAS THAT IT WILL SERVE. GENERAL RECEPTACLE
 AND LIGHTING DESIGNATION IS NOT CLEAR AND EVIDENT AS
 PER NEC 408.4
 11. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL.
 PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  