2016-04-18 11:14:26 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| |
| 1. PLEASE DELETE FROM ELECTRICAL NOTES LIST THE |
| NON-APPLICABLE NOTES FOR RESIDENTIAL DWELLINGS. |
| 2. PROVIDE A NOTE TO PROVIDE TAMPER RESISTANT |
| RECEPTACLE TO THE CLASSROOM AREAS AS SHOWN ON DRAWINGS. |
| NEC 406.14 |
| 3. CLARIFY GFCI SHOWN IN SHOWER AREA, NEC 406.9C |
| 4. ADDRESS ALL FIRE DEPARTMENT COMMENTS RELATED TO THE |
| ELECTRICAL SCOPE. |
| 5. SHOW ON DRAWINGS THE CIRCUIT DESIGNATION FOR ALL |
| POWER AND LIGHTING OUTLETS. FBC 107.3.5 |
| 6. CLARIFY ON DRAWINGS WHAT IS NEW AND WHAT IS |
| EXISTING, BY DESIGNATING N OR E AS SYMBOLS. |
| 7. SHOW ON PLANS THE LOCATION OF THE ELECTRICAL SERVICE |
| AND THE AIR HANDLER EQUIPMENT. |
| 8. PLEASE CLARIFY THE OCCUPANCY SENSORS SHOWN FOR THE |
| FAN MOTOR IN CLASSROOM. |
| 9. PROVIDE EXISTING ONE-LINE DIAGRAM AND ALL NEW |
| SERVICE EQUIPMENT WITH ASSOCIATED WIRE SIZES, CONDUIT |
| SIZE AND GROUNDING SCHEME. FBC 107.3.5 |
| 10. SHOW ON PANEL SCHEDULE THE CIRCUIT IDENTIFICATION |
| FOR THE AREAS THAT IT WILL SERVE. GENERAL RECEPTACLE |
| AND LIGHTING DESIGNATION IS NOT CLEAR AND EVIDENT AS |
| PER NEC 408.4 |
| 11. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. |