Plan Review Notes
Plan Review Notes For Permit 16040574
Permit Number 16040574
Review Stop B
Sequence Number 1
Notes
Date Text
2016-05-09 08:21:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16040574
 ADD: 1025 7TH ST.
 CONT: T. B. D. / TO BE DETEMINED
 TEL: 561-310-7829
 E-MAIL: ?????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MAY 09/ 2016
 ACTION: DENIED
  
 1) THE COVERSHEET LIST THIS BUILDING CONSTRUCTION TYPE
 AS A III-B TYPE CONSTRUCTION, SHEETS A1, A3 & A4 ALL
 SHOW THIS STRUCTURE WITH WOOD FRAME EXTERIOR WALLS.
 PLEASE REVIEW CONSTRUCTION TYPE FOR A III-B. PLANS DO
 NOT CALL OUT FOR FIRE RETARDANT TREATED WOOD FOR THE
 EXTERIOR WALL FRAMING MEMBERS OR SUB-SHEATHING.
  
 2014 FBC-B 602.3. 602.3 TYPE III. TYPE III CONSTRUCTION
 IS THAT TYPE OF CONSTRUCTION IN WHICH THE EXTERIOR
 WALLS ARE OF NONCOMBUSTIBLE MATERIALS AND THE INTERIOR
 BUILDING ELEMENTS ARE OF ANY MATERIAL PERMITTED BY THIS
 CODE. FIRE-RETARDANT-TREATED WOOD FRAMING COMPLYING
 WITH SECTION 2303.2 SHALL BE PERMITTED WITHIN EXTERIOR
 WALL ASSEMBLIES OF A 2-HOUR RATING OR LESS.
  
 2) A SURVEY IS PROVIDED FOR THE LOT THIS BUILDING IS TO
 BE BUILT UPON, BUT THERE IS NO PROPOSED BUILDING ON THE
 SURVEY SHOWING THE DIMENSIONS FROM THE PROPERTY LINES
 NOR THE REQUIRED SET BACKS. 2014 FBC-B TABLE 602 &
 TABLE 705.8.
  
 3) THE PROPOSED VALUE OF THE PROJECT IS EXTREMELY LOW
 AT $75,000.00 IN VALUE. USING THE ICC BUILDING
 VALUATION CHARTS FROM AUGUST 2015 FOR THE SQUARE
 FOOTAGE OF :
 A3/ III-B 937 SQ. FT. X $137.12 = $ 128,481.44
 B / III-B 1,631 SQ. FT. X $152.55 = $ 248,809.05
 $ 377,290.00 TOTAL VALUE FOR THE BUILDING
 ONLY!!!!!!!!!!
  
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 4A) SHEET A4/ LIFE SAFETY SHEET DOES NOT SHOW THE
 CORRIDOR AS A FIRE RATED CORRIDOR. PLEASE REVIEW TABLE
 1018.1 OF THE 2014 FBC-B. FOR BOTH ASSEMBLY AND
 BUSINESS OCCUPANCCIES OF NON-FIRE SPRINKLERED BUILDINGS
 WITH AN OCCUPANT LOAD GREATER THAN 30 A ONE HOUR FIRE
 RATED CORRIDOR IS REQUIRED WITH REQUIRED OPENING
 PROTECTIVES FOR DOORS IN COMPLIANCE OF TABLE 716.5. 20
 MINUTE FIRE RATED DOORS, SEE FOOTNOTE B.
  
 4B) PLEASE SHOW HOW THE 1 HOUR FIRE RATED CORRIDOR IS
 TO BE BUILT INCLUDING THE FIRE RATING OF WALLS TO THE
 ROOF SHEATHING ON BOTH SIDES OF THE COORIDOR OR IS
 THERE GOING TO BE A FIRE RATED CEILING ASSEMBLY? THE
 MECHANICAL SHEET M1 DOES NOT SHOW EITHER THE DUCTS
 PENETRATING THE CORRIDOR CEILING WITH FIRE DAMPERS.
 DEPENDING WHERE THE MAIN TRUNK LINE IS PLACED IF ABOVE
 IN THE ATTIC OR BELOW A RATED CORRIDOR CEILING EITHER
 CEILING DAMPERS WILL BE REQUIRED OR FIRE DAMPERS IN THE
 CORRIDOR WALLS. SEE FBC-B 717.5.4.1 CORRIDORS. A LISTED
 SMOKE DAMPER DESIGNED TO RESIST THE PASSAGE OF SMOKE
 SHALL BE PROVIDED AT EACH POINT A DUCT OR AIR TRANSFER
 OPENING PENETRATES A CORRIDOR ENCLOSURE REQUIRED TO
 HAVE SMOKE AND DRAFT CONTROL DOORS IN ACCORDANCE WITH
 SECTION 716.5.3.
  
 5) DISCREPANCY IN PLANS. THE COVERSHEET SHEET INDEX
 LIST SHEETS A1-A6 WHERE AS IN THE SET OF DRAWINGS THERE
 ARE 3 SHEETS LABELED A4, NO A5 OR A6. PLEASE CORRECT
 THE DISCREPANCY (TYPO) IN PLANS. 107.2.1.3
  
 6) FOUNDATIONSHEET (A5) VERSES SHEET A3 DETAIL 14 CUT
 SECTION OF EXTERIOR WALL AND FOUNDATION. SHEET A5 THE
 PERIMTETER FOUNDATION IS INDICATED AS 18 IN. WIDE X
 16IN. DEEP. PLEASE SEE SHEET A3 DETAIL # 14. THE FINISH
 FLOOR IS SHOWN AT ELE. 0-0 FT. THE BOTTOM SILL PLATE IS
 RECESSED, THE DIMINSION NOT GIVEN. THE STUCCO SIDING
 AND SUB-SHEATHING STOP ABOVE THE BOTTOM HALF OF THE
 BOTTOM SILL PLATE NOT PROVIDING PROTECTION AGAINST THE
 WEATHER AND PROMOTING ROT. THE 2012 ICC-B CODE
 COMMENTARY 2304.11.2.6 ON THIS SECTION INDICATES THE
 STUCCO AND SHEATHING SHOULD EXTEND AT LEAST 1 INCH
 BELOW THE TOP OF THE FOUNDATION. THEN THE 6 INCH
 CLEARANCE BETWEEN THE STUCCO AND SUB-SHEATHING TO
 EXPOSED GRADE SHOLD OCCUR. SECTION 1809.4 OF THE 2014
 FBC-B REQUIRES THE FOUNDATION TO BE A MINIMUM OF 12
 INCHES BELOW GRADE TO THE BOTTOM OF THE FOUNDATION. THE
 VERTICAL DIMENSION OF THE FOUNDATION NEEDS TO BE
 INCREASED TO MEET ALL OF THESE CODE REQUIREMENTS.
  
 7) SHEET A3 DETAIL 14 ALSO INDICATES THE USE OF STUCCO
 AND THE USE OF WIRE LATH. PLEASE SHOW COMPLIANCE WITH
 2014 FBC-B 2510.6 WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION 1404.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 1405.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 8) DISCREPANCY IN PLANS. SHEET A2.2 THE ELEVATIONS
 SHOWS A 2FT OVERHANG FOR THE ROOF TRUSSES WHEREAS SHEET
 A3 DETAIL 14 SHOWS ONLY A 1FT. 4 IN. OVERHANG. SHEET
 A-6 (SHOWN AS A-4) THE TRUSS LAYOUT SHEET DOES NOT SHOW
 ANY DIMENSION AS FAR AS WHAT THE OVERHANG SHOULD BE?
 107.2.1.3.
  
 9) SHEET A-6 (SHOWN AS A-4) THE TRUSS LAYOUT SHEET
 SHOWS WHAT APPEARS TO BE A 2 FT. OVERHANG ON THE GABLE
 END WALLS, THIS DETAIL MAY BE REQUIRED TO BE A DROPPED
 GABLE END. PLEASE NOTE THIS TYPE OF LATTER TYPE
 OVERHANG IS USSUALLY FOUND ON TRUSS OVERHANGS OF 12
 INCHES. THE WOOD WOOD TRUSSES SHALL BE DESIGNED IN
 ACCORDANCE WITH SECTION 2303.4.
  
 2303.4.2 TRUSS PLACEMENT DIAGRAM. THE TRUSS
 MANUFACTURER SHALL PROVIDE A TRUSS PLACEMENT DIAGRAM
 THAT IDENTIFIES THE PROPOSED LOCATION FOR EACH
 INDIVIDUALLY DESIGNATED TRUSS AND REFERENCES THE
 CORRESPONDING TRUSS DESIGN DRAWING. THE TRUSS PLACEMENT
 DIAGRAM SHALL BE PROVIDED AS PART OF THE TRUSS
 SUBMITTAL PACKAGE, AND WITH THE SHIPMENT OF TRUSSES
 DELIVERED TO THE JOB SITE. TRUSS PLACEMENT DIAGRAMS
 THAT SERVE ONLY AS A GUIDE FOR INSTALLATION AND DO NOT
 DEVIATE FROM THE PERMIT SUBMITTAL DRAWINGS SHALL NOT BE
 REQUIRED TO BEAR THE SEAL OR SIGNATURE OF THE TRUSS
 DESIGNER.
  
 2303.4.3 TRUSS SUBMITTAL PACKAGE. THE TRUSS SUBMITTAL
 PACKAGE PROVIDED BY THE TRUSS MANUFACTURER SHALL
 CONSIST OF EACH INDIVIDUAL TRUSS DESIGN DRAWING, THE
 TRUSS PLACEMENT DIAGRAM, THE PERMANENT INDIVIDUAL TRUSS
 MEMBER RESTRAINT/BRACING METHOD AND DETAILS AND ANY
 OTHER STRUCTURAL DETAILS GERMANE TO THE TRUSSES; AND,
 AS APPLICABLE, THE COVER/TRUSS INDEX SHEET.
  
 10) PLEASE NOTE SHEET A2.1 AND A4 BOTH SHOW THIS
 STRUCTURE HAVING A GABLE END ON BOTH ENDS OF THE
 BUILDING. THERE ARE NO DETAILS ON SHEET A4 FOR THE
 GABLE END WALL BRACING OF THE TOP CORD, END TRUSS WALL
 TO THE BOTTOM CORD OF TRUSSES BEING TRANSFERRED INTO
 THE WOOD FRAME BEARING WALL. FBC-B 2308.3.2.2. WHERE
 ROOF TRUSSES ARE USED AND ARE INSTALLED PERPENDICULAR
 TO AN EXTERIOR BRACED WALL LINE, LATERAL FORCES SHALL
 BE TRANSFERRED FROM THE ROOF DIAPHRAGM TO THE BRACED
 WALL OVER THE FULL LENGTH OF THE BRACED WALL LINE BY
 BLOCKING OF THE ENDS OF THE TRUSSES OR BY OTHER
 APPROVED METHODS PROVIDING EQUIVALENT LATERAL FORCE
 TRANSFER. BLOCKING SHALL BE MINIMUM 2 INCHES (51 MM)
 NOMINAL THICKNESS AND SHALL EXTEND TO WITHIN 2 INCHES
 (51 MM) FROM THE ROOF SHEATHING ABOVE AND SHALL BE
 FASTENED TO THE BRACED WALL LINE TOP PLATE AS SPECIFIED
 IN TABLE 2304.9.1, ITEM 11. NOTCHING OR DRILLING OF
 HOLES IN BLOCKING IN ACCORDANCE WITH THE REQUIREMENTS
 OF SECTION 2308.8.2 OR SECTION 2308.10.4.2 SHALL BE
 PERMITTED.
  
 11) DISCREPANCY IN PLANS SHEET A2.1 SHOWS WALL AND ROOF
 ZONES PRESSURES FOR ZONES 1-5. THE CHART DOES NOT
 INDICATE IF THERE PRESSURES ARE IN VULT OR VASD. PLEASE
 ALSO REVIEW PRESSURES FOUND ON A-5 DETAIL 3 THE DETAIL
 SHOWS A HIP ROOF NOT A GABLE ROOF. THE PRESSURES FOR
 ZONES 2 AND 3 ARE THE SAME, THIS IS NOT TRUE FOR A
 GABLE ROOF!!! 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 12) SHEET A2 NOR A3 DETAIL 14 SHOW COMPLIANCE WITH:
 PLEASE PROVIDE ATTIC VENTILATIONS CALCULATIONS IN
 COMPLIANCE WITH 2308.10.11 ATTIC VENTILATION. FOR ATTIC
 VENTILATION, SEE SECTION 1203.2.
  
 13) SHEET A2.1 THE SOUTH ELEVATION SHOWS ARCHITECTURAL
 DETAILS OF COLUMNS AND PEDIMENT PLEASE SHOW A CUR
 THROUGH SECTION OF THIS AREA FOR A BETTER UNDERSTANDING
 OF THE DEPTH OF THESE ELEMENTS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 14) ROOFING: NOTICE: EFFECTIVE APRIL 1/2016 THE
 REFERENCED MIAMI-DADE COUNTY ELECTROGALVANIZED
 FASTENERS LISTINGS ARE SUSPENDED:
 11--1019.02 & 11-1019.03 BLUELINX CORP.
 12-0423.06 CONTINENAL MATERIALS, INC.
 15-1123.04 PRIME SOURCE BUILDING PRODUCTS, INC.
 13-0530.01 SPECIALTY FASTENING SYSTEM
 12-0423.03 & 12-0423.04 SUMMIT CONGLOMERATE, LLC
 12-1205.11, 12-1205.13 & 13-05 & 13-0514.05 WEATHERPRO,
 LLC
  
 15) PLEASE SHOW COMPLIANCE WITH THE 2014 ENERGY CODE:
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
  
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
  
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
  
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  