2016-04-15 13:20:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE LABEL RECEPTACLES IN THE UTILITY, RESTROOMS
 AND DRINKING FOUNTAIN TO BE GFCI PROTECTED. NEC
 210.8B(2) AND (5) AND NEC 422.52
 2. SIGNATURE IS REQUIRED ON DRAWINGS BY AOR.
 3. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  